61
Alarm
T&H-com-flt
Possible
reason
If the inverter is equipped with heating and dehumidification function and the
communication between the temperature & humidity board and the device is
poor, this alarm occurs
Measure
Contact Sungrow
Remark
The operation LED is green.
10.5 Other Faults
Fault
Inverter shuts down shortly after start-up
Possible
reason
DC input voltage just reaches the inverter start-up voltage. The voltage will
decrease and inverter will stop when it is under load.
Measure
Design the serial and parallel connection in accordance with the open circuit
voltage; increase the input DC voltage; avoid adopting the critical voltage
Remark
-
Fault
LCD Display Cannot Start or Stop Inverter
Possible
reason
Communication malfunction between the LCD display and the DSP; LCD power
supply malfunction
Measure
Check the connection between the LCD display and the DSP when inverter is
voltage-free
Remark
-
Fault
Communication Failure with PC
Possible
reason
Possible reasons are various. Please refer to the Measure for troubleshooting
Measure
Check if the address and the Baud rate of the LCD are the same with that of
PC
Check to ensure the circuits are properly connected and if the RS485
communication is adopted, the A and B ports are connected correctly
Check if the communication converters are matched. Communicate again
after replacing the converter
The monitor disk is installed incorrectly. It is recommended to reinstall the
disk
If all the above-mentioned items are correct and this fault continues, please
replace the PC communication module on the LCD display
Remark
The monitor disk might be incompatible with the antivirus software and thus
cannot be installed correctly. You are recommended to disable the antivirus
software and then install the monitor software.
If the fault still occurs, please contact Sungrow

Table of Contents

Other manuals for Sungrow SG1250UD

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Sungrow SG1250UD and is the answer not in the manual?

Sungrow SG1250UD Specifications

General IconGeneral
BrandSungrow
ModelSG1250UD
CategoryInverter
LanguageEnglish

Related product manuals