EasyManuals Logo
Home>Sungrow>Inverter>SG40CX

Sungrow SG40CX User Manual

Sungrow SG40CX
129 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #53 background imageLoading...
Page #53 background image
43
The inverter has not been tested to AS/NZS 4777.2:2020 for multiple inverter combinations.
MV Transformer
The MV transformer used together with the inverter should meet the following requirements:
A distribution transformer can be used if it is designed for the typical cyclical loads of a
PV system (there is load in the day and no load at night).
A liquid-immersed type transformer or a dry type transformer can be used, and the shield
winding is not a requisite.
The line-to-line voltage on the LV side of the transformer should endure the output volt-
age of inverter. When the transformer is connected to the IT grid, to-ground withstanding
voltage of the LV winding of the transformer, the LV side AC cables, and the LV side sec-
ondary equipment (including the relay protection device, detection & measuring device,
and other related auxiliary devices) should not be lower than 1,100V.
The line-to-line voltage on the HV side of the transformer should comply with the local
power grid voltage.
A transformer with a tap changer on the HV side is recommended in order to keep the
voltage consistent with the grid voltage.
At an ambient temperature of 45, the transformer can run in 1.1 times of load for long
time.
A transformer with a short-circuit impedance 6% (permissible tolerance: ±10%) is
recommended.
The voltage drop of system cable is no more than 3%.
The DC component that the transformer can withstand is 1% of the fundamental current
at rated power.
For thermal rating, the load curve of the transformer and environment conditions should
be taken into account.
The apparent power of the inverter should never exceed the power of the transformer.
The maximum AC current of all inverters connected in parallel must be taken into ac-
count. It is recommended that the total number of inverters that are connected to the grid
not exceed 30.
The transformer must be protected against overloading and short circuit.
The transformer is an important part of grid-connected PV generation system. The fault
tolerance capacity of the transformer should be taken into account at all times. The fault
include: system short circuit, grounding fault, voltage drop, etc.
Take ambient temperature, relative humidity, altitude, air quality, and other environmental
conditions into account when selecting and installing the transformer.
5.6.2 Requirements for OT/DT Terminal
OT/DT terminals (not included in the delivery scope) are required for fixing AC cables to the
terminal block. Purchase the OT/DT terminals according to the following requirements.
Specification: M8;
User Manual 5 Electrical Connection

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Sungrow SG40CX and is the answer not in the manual?

Sungrow SG40CX Specifications

General IconGeneral
BrandSungrow
ModelSG40CX
CategoryInverter
LanguageEnglish

Related product manuals