EasyManuals Logo
Home>Thytronic>Protection Device>NG10

Thytronic NG10 User Manual

Thytronic NG10
158 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #14 background imageLoading...
Page #14 background image
TECHNICAL DATA
14
NG10 - Manual - 04 - 2022
Type tests IEC 60255-1
3.2 INPUT CIRCUITS
Auxiliary power supply Uaux
Voltage
Nominal value (range)
[1]
24...48 V~/- or 115...230 V~/110...220 V-
Operative range (each one of the above nominal values) 19...60 V~/- or 85...265 V~/75...300 V-
Inrush current (max)
24 V- 6 A, 5 ms
48 V- 14 A, 5 ms
110 V- 20 A, 1 ms
230 V~ 50 A, 1 ms
Frequency (for alternate voltage supply) 45...66 Hz
Max distortion factor ( for alternating voltage supply) 15%
Max alternating component (for dc voltage supply):
Full wave rectified sine wave 100 %
Sine wave 80 %
Power consumption:
Maximum (energized relays, Ethernet TX) 10 W (20 VA)
Maximum (energized relays, Ethernet FX) 15 W (25 VA)
Phase current input circuits (side H and side L)
Relay nominal phase current I
nH
and I
nL
1 A or 5 A selectable by dip-switch
Permanent overload 25 A
Thermal overload (1 s) 500 A
Dynamic overload (half cycle) 1250 A
Rated consumption (for any phase) 0.002 VA with I
nH or
I
nH
= 1 A
0.04 VA with I
nH or
I
nH
= 5 A
Residual current input circuit
Relay nominal residual current I
En
1 A or 5 A selectable by dip-switch
Permanent overload 25 A
Thermal overload (1 s) 500 A
Dynamic overload (half cycle) 1250 A
Rated consumption 0.006 VA with I
En
= 1 A
0.12 VA with I
En
= 5 A
Binary input circuits
Quantity 2
Type optocoupler
Operative range 24...265 V~/-
Min activation voltage 18 V
Max consumption, energized 3 mA
ON delay time OFF->ON (IN1 t
ON
, IN2 t
ON
) 0.00...100.0 s
0.00...9.99 s
10.0...100.0 s
OFF delay time ON->OFF (IN1 t
OFF
, IN2 t
OFF
) 0.00...100.0 s
0.00...9.99 s (step 0.01 s)
10.0...100.0 s (step 0.1 s)
Block input (Logic selectivity)
Quantity 1
Type polarized wet input (powered by internal isolated supply)
Max consumption, energized 5 mA
3.3 OUTPUT CIRCUITS
Relays
Quantity 6
Type of contacts K1, K2 changeover (SPDT, type C)
Type of contacts K3, K4, K5 make (SPST-NO, type A)
Type of contacts K6 break (SPST-NC, type B)
Nominal current 8 A
Nominal voltage/max switching voltage 250 V~/400 V~
Breaking capacity:
Direct current (L/R = 40 ms) 50 W
Alternating current (l = 0,4) 1250 VA
Make 1000 W/VA
Short duration current (0,5 s) 30 A
Minimum switching load 300 mW (5 V/ 5 mA)
Life:
Mechanical 10
6
operations
Electrical 10
5
operations
Note 1 Version must be selected at ordering

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Thytronic NG10 and is the answer not in the manual?

Thytronic NG10 Specifications

General IconGeneral
BrandThytronic
ModelNG10
CategoryProtection Device
LanguageEnglish

Related product manuals