TECHNICAL DATA
14
NG10 - Manual - 04 - 2022
Type tests IEC 60255-1
3.2 INPUT CIRCUITS
Auxiliary power supply Uaux
Voltage
Nominal value (range)
[1]
24...48 V~/- or 115...230 V~/110...220 V-
Operative range (each one of the above nominal values) 19...60 V~/- or 85...265 V~/75...300 V-
Inrush current (max)
• 24 V- 6 A, 5 ms
• 48 V- 14 A, 5 ms
• 110 V- 20 A, 1 ms
• 230 V~ 50 A, 1 ms
Frequency (for alternate voltage supply) 45...66 Hz
Max distortion factor ( for alternating voltage supply) 15%
Max alternating component (for dc voltage supply):
• Full wave rectified sine wave 100 %
• Sine wave 80 %
Power consumption:
• Maximum (energized relays, Ethernet TX) 10 W (20 VA)
• Maximum (energized relays, Ethernet FX) 15 W (25 VA)
Phase current input circuits (side H and side L)
Relay nominal phase current I
nH
and I
nL
1 A or 5 A selectable by dip-switch
Permanent overload 25 A
Thermal overload (1 s) 500 A
Dynamic overload (half cycle) 1250 A
Rated consumption (for any phase) ≤ 0.002 VA with I
nH or
I
nH
= 1 A
≤ 0.04 VA with I
nH or
I
nH
= 5 A
Residual current input circuit
Relay nominal residual current I
En
1 A or 5 A selectable by dip-switch
Permanent overload 25 A
Thermal overload (1 s) 500 A
Dynamic overload (half cycle) 1250 A
Rated consumption ≤ 0.006 VA with I
En
= 1 A
≤ 0.12 VA with I
En
= 5 A
Binary input circuits
Quantity 2
Type optocoupler
Operative range 24...265 V~/-
Min activation voltage 18 V
Max consumption, energized 3 mA
ON delay time OFF->ON (IN1 t
ON
, IN2 t
ON
) 0.00...100.0 s
0.00...9.99 s
10.0...100.0 s
OFF delay time ON->OFF (IN1 t
OFF
, IN2 t
OFF
) 0.00...100.0 s
0.00...9.99 s (step 0.01 s)
10.0...100.0 s (step 0.1 s)
Block input (Logic selectivity)
Quantity 1
Type polarized wet input (powered by internal isolated supply)
Max consumption, energized 5 mA
3.3 OUTPUT CIRCUITS
Relays
Quantity 6
Type of contacts K1, K2 changeover (SPDT, type C)
Type of contacts K3, K4, K5 make (SPST-NO, type A)
Type of contacts K6 break (SPST-NC, type B)
Nominal current 8 A
Nominal voltage/max switching voltage 250 V~/400 V~
Breaking capacity:
• Direct current (L/R = 40 ms) 50 W
• Alternating current (l = 0,4) 1250 VA
Make 1000 W/VA
Short duration current (0,5 s) 30 A
Minimum switching load 300 mW (5 V/ 5 mA)
Life:
• Mechanical 10
6
operations
• Electrical 10
5
operations
Note 1 Version must be selected at ordering