TECHNICAL DATA
21
NG10 - Manual - 04 - 2022
3.9 METERING
More data are available inside Section 5 - MEASURES, LOGIC STATES AND COUNTERS
Accuracy (type tests)
MEASURE Reference values
Accuracy
Reference values
Accuracy
Phase current 0.1 I
n
0.2% 1 I
n
0.03%
Measured residual current 0.01 I
En
0.3% 1 I
En
0.02%
Frequency 0.02 U
n
3 mHz 1 U
n
2 mHz
Pickup and operate time 1.5 x setting for fist element 5% ± 10 ms 2.5 x setting for other elements 5% ± 10 ms
Measures
Direct
Frequency (f )
RMS value of fundamental component for phase currents side H (I
L1H
, I
L2H
, I
L3H
)
RMS value of fundamental component for phase currents side L (I
L1L
, I
L2L
, I
L3L
)
RMS value of fundamental component for measured residual current (I
E
)
Calculated
Calculated residual currents side H (I
EH
)
Maximum current between I
L1
-I
L2
-I
L3
side H and side L
(I
LMAXH
, I
LMAXL
)
Minimum current between I
L1
-I
L2
-I
L3
side H and side L (I
LMINH
, I
LMINL
)
Average current between side H and side L
(I
LH
, I
LL
)
Compensated phase currents side H (I
L1cH
, I
L2cH
, I
L3cH
)
Compensated phase currents side L (I
L1cL
, I
L2cL
, I
L3cL
)
Stabilization currents (87 element) (I
SL1
, I
SL2
, I
SL3
)
Differential phase currents (I
dL1
, I
dL2
, I
dL3
)
(H) Stabilization current (64REF-1 element) side H (I
ESH
)
Demand phase
Phase fixed currents demand side H (I
L1FIXH
, I
L2FIXH
, I
L3FIXH
)
Phase fixed currents demand side L (I
L1FIXL
, I
L2FIXL
, I
L3FIXL
)
Phase rolling currents demand side H (I
L1ROLH
, I
L2ROLH
, I
L3ROLH
)
Phase rolling currents demand side L (I
L1ROLL
, I
L2ROLL
, I
L3ROLL
)
Phase peak currents demand side H (I
L1MAXH
, I
L2MAXH
, I
L3MAXH
)
Phase peak currents demand side L (I
L1MAXL
, I
L2MAXL
, I
L3MAXL
)
Phase minimum currents demand side H (I
L1MINH
, I
L2MINH
, I
L3MINH
)
Phase minimum currents demand side L (I
L1MINL
, I
L2MINL
, I
L3MINL
)
PT100
[1]
Temperature PT1 (T
1
)
Temperature PT2 (T
2
)
Temperature PT3 (T
3
)
Temperature PT4 (T
4
)
Temperature PT5 (T
5
)
Temperature PT6 (T
6
)
Temperature PT7 (T
7
)
Temperature PT8 (T
8
)
Note 1 The measures of temperature are available only when the MPT module on Thybus is enabled (eight Pt100 inputs)