EasyManuals Logo
Home>Thytronic>Protection Device>NG10

Thytronic NG10 User Manual

Thytronic NG10
158 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #16 background imageLoading...
Page #16 background image
TECHNICAL DATA
16
NG10 - Manual - 04 - 2022
3.6 GENERAL SETTINGS
Rated values (Base)
Relay nominal frequency (f
n
) 50, 60 Hz
Relay phase nominal current side H and L (I
nH
and I
nH
) 1 A or 5 A
[1]
Phase CT primary nominal current side H and L (I
npH
and I
npH
) 1 A...20.0 kA
1...499 A (step 1 A)
500...4990 A (step 10 A)
5000...20000 A (step 100 A)
Relay residual nominal current (I
En
) 1 A o 5 A
[1]
Residual CT primary nominal current (I
Enp
) 1 A...20.0 kA
1...499 A (step 1 A)
500...4990 A (step 10 A)
5000...20000 A (step 100 A)
Protected device nominal current (I
ng
) 1 A...20 kA
1...499 A (step 1 A)
500...4990 A (step 10 A)
5000...20000 A (step 100 A)
Primary nominal current chosen as referrence (I
nref
)
[2]
- A
Lato di riferimento per la compensazione (Refsize)
[2]
-
Current matching type (MatchType) INTERNAL/EXTERNAL
Protected object by differential protection (ProtObj) GEN-MOT-LINE-BAR
Input sequence
[3]
Phase current sequence side H (I-SequenceH) IL1-IL2-IL3 Default
IL1-IL3-IL2
IL2-IL1-IL3
IL2-IL3-IL1
IL3-IL1-IL2
IL3-IL2-IL2
Phase current sequence side L (I-SequenceL) IL1-IL2-IL3 Base
IL1-IL3-IL2
IL2-IL1-IL3
IL2-IL3-IL1
IL3-IL1-IL2
IL3-IL2-IL2
Polarity
[3]
C09-C10 (IL1H) terminal polarity (C09-C10 POL) NORMAL/REVERSE
C11-C12 (IL2H) terminal polarity (C11-C12 POL) NORMAL/REVERSE
C13-C14 (IL3H) terminal polarity (C13-C14 POL) NORMAL/REVERSE
C15-C16 (IE1) terminal polarity(C15-C16 POL) NORMAL/REVERSE
C01-C02 (IL1L) (terminal polarity C01-C02 Pol) NORMAL/REVERSE
C03-C04 (IL2L) terminal polarity (C03-C04 POL) NORMAL/REVERSE
C05-C06 (IL3L) terminal polarity (C05-C06POL) NORMAL/REVERSE
C07-C08 (IL3L) terminal polarity (C07-C08POL) NORMAL/REVERSE
Note 1 The nominal current settings doesn’t concern the protection elements; they must agree with hardware setting (dip-switch 1 A or 5 A) .
Note 2 Calculated by relay (L or H)
Nota 3 Adjusting enabled by working with session-level 1

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Thytronic NG10 and is the answer not in the manual?

Thytronic NG10 Specifications

General IconGeneral
BrandThytronic
ModelNG10
CategoryProtection Device
LanguageEnglish

Related product manuals