E6582175
F-18
6
6.3 Selecting control mode
pt : V/F control mode selection
Function
The V/F controls shown below can be selected.
V/F constant
Variable torque
Automatic torque boost control *1
Vector control *1
Energy saving *1
Dynamic energy-saving (For fan and pump)
PM motor control
V/F 5-point setting
*1 Parameter setting macro torque boost:  parameter can automatically set this parameter and
auto-tuning at a time. (Refer to section 6.1.5)
[Parameter setting]
Title Function Adjustment range Default setting

V/F control mode selection
0: V/F constant
1: Variable torque
2: Automatic torque boost control
3: Vector control
4: Energy-saving
5: Dynamic energy-saving
(For fan and pump)
6: PM motor control
7: V/F 5-point setting
8: - *3
*2
*2: Default setting values vary depending on the setup menu setting. Refer to section 11.5.
*3: 8 is manufacturer setting parameter. Do not change the value of this parameter.
Note:  (V/F control mode selection) is valid only for the first motor.
Changes to "V/F constant control" when switching to the second motor, regardless of the  setting.

Table of Contents

Other manuals for Toshiba Tosvert VF-S15

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Toshiba Tosvert VF-S15 and is the answer not in the manual?

Toshiba Tosvert VF-S15 Specifications

General IconGeneral
BrandToshiba
ModelTosvert VF-S15
CategoryInverter
LanguageEnglish

Related product manuals