E6582175
F-54
6
6.16 Bumpless operation
f295 : Bumpless operation selection
f732 : Local/remote key prohibition of extension panel
f750 : Easy key function selection
Function
When switching from Remote mode to Local mode, the status of start and stop, and operating
frequency at Remote mode are moved to Local mode.
Running status of Local mode will not moved to Remote mode when switching from Local mode to
Remote mode.
[Parameter setting]
Title Function Adjustment range Default setting
f295
Bumpless operation selection
0: Disabled
1: Enabled
0
f732
Local/remote key prohibition of
extension panel
0: Permitted
1: Prohibited
1
EASY key function selection
0: Easy / standard setting mode
switching function
1: Shortcut key
2: Local / remote key
3: Monitor peak / minimum hold
trigger
4: -
5: -
0
● Set Local/remote function to key.
f750 (EASY key function selection) = 2 (Local / remote key).
EASY lamp is lighting during local mode.
● Local mode is the operation using operation panel.
Remote mode is the operation method selected by the command mode selection: cmod and Frequency
setting mode selection: fmod
● LOC/REM key of extension panel option (RKP007Z) is available.
In this case, set parameter f732 (Local/remote key prohibition of extension panel) = 0 (Permitted).
EASY