E6582175
F-49
6
Note1: Nearly the same motor shaft fixing control can be exercised when entering a DC braking command with the
signal at an input terminal.
Note2: If a power failure occurs during motor shaft fixing control and the motor starts to coast, motor shaft
fixing control will be canceled.
Also, if the inverter trips during motor shaft fixing control and is restored to working order by the retry
function, motor shaft fixing control will be canceled.
Note 3: During shaft fixing control, the carrier frequency becomes the setting of whichever is lower parameter,
f249 or f300.
6.13 Stop at lower-limit frequency operation (sleep function)
f256 : Time limit for lower-limit frequency operation
f259 : Lower limit frequency reach time limit at start-up
f391 : Hysteresis for lower-limit frequency operation
Function
If operation at the lower-limit frequency () is carried out for the time set with , the inverter will
automatically decelerate the motor to stop for the purpose of energy-saving. At that time, “” is
displayed (alternately) on the operation panel.
Stop by this function will be canceled if a frequency command value exceeds the lower-limit frequency
(ll) f391 (Hz), or if the operation command is OFF. This function will not work until the output
frequency reaches ll at the start of operation.
If the output frequency doesn’t reach ll at the start of operation for malfunction of load, the inverter will
automatically stop after the time set with f259 elapses.
[Parameter setting]
Title Function Adjustment range Default setting
f256
Time limit for lower-limit frequency
operation
0.0: Disabled
0.1 - 600.0 (s)
0.0
f259
Lower limit frequency reach time limit at
start-up
0.0: Disabled
0.1 - 600.0 (s)
0.0
f391
Hysteresis for lower-limit frequency
operation
0.0-ul (Hz) 0.2

Table of Contents

Other manuals for Toshiba Tosvert VF-S15

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Toshiba Tosvert VF-S15 and is the answer not in the manual?

Toshiba Tosvert VF-S15 Specifications

General IconGeneral
BrandToshiba
ModelTosvert VF-S15
CategoryInverter
LanguageEnglish

Related product manuals