Note: This function is valid when doing forward/reverse switching.
When starting operation, f256 function will not work until output frequency reaches ll.
When the output frequency exceeds ll, f259 function will be invalid until operation signal is OFF.
6.14 Jog run mode
f260 : Jog run frequency
f261 : Jog run stopping pattern
f262 : Panel jog run mode
Function
Use the jog run parameters to operate the motor in jog mode. Input of a jog run signal immediately
generates a jog run frequency output irrespective of the designated acceleration time.
Also, you can choose the jog run start/stop mode from the panel.
Assign 18: jog run mode to an input terminal.
Ex) When assigning it to the RES terminal: f113 to 18.
The motor can be operated in jog mode while the assigned input terminals are connected (RES-CC ON).
[Parameter setting]
Title Function Adjustment range Default setting
f260
Jog run frequency f240-20.0 (Hz) 5.0
f261
Jog run stopping
pattern
0: Deceleration stop
1: Coast stop
2: DC braking
0
f262
Panel jug run mode
0: Invalid
1: Valid
0
Output frequency [Hz]
Time[s]
ON
OFF
ll+f391
ll
Forward/ reverse