E6582175
K-8
11
Frequency parameters
Title
Communication
No.
Function Unit
Minimum
setting unit
Panel/Commun
ication
Adjustment range
Default
setting
User
setting
Reference

0200 Frequency priority
selection
- - 0:  (Switchable to  by
terminal input)
0
5.8
6.10.1
1:  (Switchable to  at
1.0Hz or less of designated
frequency)

0201 VIA input point 1
setting
% 1/1 0-100 0
6.10.2
7.3

0202 VIA input point 1
frequency
Hz 0.1/0.01 0.0-500.0 0.0

0203 VIA input point 2
setting
% 1/1 0-100 100

0204 VIA input point 2
frequency
Hz 0.1/0.01 0.0-500.0 *1

0205 VIA input point 1
rate
% 1/0.01 0-250 0 6.31

0206 VIA input point 2
rate
% 1/0.01 0-250 100

0207 Frequency setting
mode selection 2
- - 0-14 (Same as ) 1
5.8
6.10.1

0209 Analog input filter ms 1/1 2-1000 64
6.10.2

0210 VIB input point 1
setting
% 1/1 -100-+100 0 7.3

0211 VIB input point 1
frequency
Hz 0.1/0.01 0.0-500.0 0.0

0212 VIB input point 2
setting
% 1/1 -100-+100 100

0213 VIB input point 2
frequency
Hz 0.1/0.01 0.0-500.0 *1

0214 VIB input point 1
rate
% 1/0.01 -250-+250 0 6.31
6.32

0215 VIB input point 2
rate
% 1/0.01 -250-+250 100

0216 VIC input point 1
setting
% 1/1 0-100 20 6.10.2
7.3

0217 VIC input point 1
frequency
Hz 0.1/0.01 0.0-500.0 0.0

0218 VIC input point 2
setting
% 1/1 0-100 100

0219 VIC input point 2
frequency
Hz 0.1/0.01 0.0-500.0 *1

0220 VIC input point 1
rate
% 1/0.01 0-250 0 6.31

0221 VIC input point 2
rate
% 1/0.01 0-250 100

0239 Factory specific
coefficient 2A
- - - -
* 3

0240 Starting frequency Hz 0.1/0.01 0.1-10.0 0.5 6.11.1

0241 Operation starting
frequency
Hz 0.1/0.01 0.0- 0.0 6.11.2

0242 Operation starting
frequency
hysteresis
Hz 0.1/0.01 0.0- 0.0

0243 Stop frequency
setting
Hz 0.1/0.01 0.0: Same as 
0.1-30.0
0.0 6.11.1
*1: Default setting values vary depending on the setup menu setting. Refer to section 11.5.
*3: Factory specific coefficient parameters are manufacturer setting parameters. Do not change the value of these parameters.

Table of Contents

Other manuals for Toshiba Tosvert VF-S15

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Toshiba Tosvert VF-S15 and is the answer not in the manual?

Toshiba Tosvert VF-S15 Specifications

General IconGeneral
BrandToshiba
ModelTosvert VF-S15
CategoryInverter
LanguageEnglish

Related product manuals