Other Ultra Data from Status Tab
The iSTAR Controller dialog box Status tab in the C•CURE 9000, shown in Figure 6-24 on
page 6-27, indicates encryption status plus other information about the Ultra.
Figure 6-24: Controller Dialog Box- Status Tab
Voltage Requirements and Distance
To operate properly, each reader requires the following minimum voltage:
A standard RM Series Reader or RM-4 board requires at least 7.5 volts.
An RM-4E board requires at least 11 volts.
The iSTAR Ultra supplies 12 volts at its reader connectors; however, the amount of voltage
that reaches the reader is affected by the following:
Number of devices on the bus
Current draw of each device
Wiring length between the devices and iSTAR Ultra
Wire gauge that connects the devices
State of the battery (if running on apS)