EasyManuals Logo
Home>VAT>Control Unit>653 Series

VAT 653 Series User Manual

VAT 653 Series
129 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #100 background imageLoading...
Page #100 background image
ERROR! REFERENCE SOU
RCE NOT FOUND.
Series
65
100/129
Edition 2019-05-03 963283EA
When ‘safety mode’ is entered from operation (i.e. pressure control mode), the unit will automatically
switch to position control mode and remain at current position. Once motor interlock is deactivated the
unit remains in position control mode.
5.7 Operation during power up
Valve position
before
power up:
Reaction of valve:
Valve power up configuration = closed
(default)
Valve power up configuration = open
Closed (isolated) Valve remains closed.
Display shows ‘C C’.
Homing will be done when first
movement command is received.
Valve runs to maximum throttle position
to detect the limit stops to do homing.
Display shows configuration of product
resp. ‘Ho’ until homing is done.
Valve position after power up is
‘A. 0’ min. conductance.
All other than closed
(not isolated)
Valve runs to max. throttle position to detect limit stop for homing. Display shows
configuration of product resp. ‘Ho’ until homing is done, and afterwards to close
position. Display shows ‘C C’.
Valve position after power up is closed Valve position after power up is open
Refer also to chapter: «Display information».
5.8 Behavior in case of power failure
Valve position
before
power failure:
Reaction of valve:
Without Power Failure Option (PFO)
653 . . - . . G . - . . . .
653 . . - . . A . - . . . .
653 . . - . . T . - . . . .
653 . . - . .
V
. - . . . .
With Power Failure Option (PFO)
653 . . - . . H . - . . . .
653 . . - . . C . - . . . .
653 . . - . . U . - . . . .
653 . . - . .
W
. - . . . .
Closed (isolated) Valve remains closed.
Valve will close or open depending
on valve configuration 1).
Default is not defined.
Display indicates F.
Valve open or in any
intermediate position
Sealing ring moves down and blocks
the pendulum plate at the current
position.
1) Provide that battery pack of the VAT controller is charged. Charging time after power up is 2 minutes
max..
All parameters are stored in a power fail save memory.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the VAT 653 Series and is the answer not in the manual?

VAT 653 Series Specifications

General IconGeneral
BrandVAT
Model653 Series
CategoryControl Unit
LanguageEnglish

Related product manuals