ProtoNode FPC-N34 & FPC-N35 User Manual
APPENDIX B: EQUIPMENT MONITOR AND CONTROL POINT DEFINITIONS
OMM-0150_B • 5/20/2021 Technical Support • (800) 526-0288 • Mon-Fri, 8 am - 5 pm EST Page 67 of 140
Appendix B-5: AM Series Point Definitions
For all devices, empty or not, available holding registers return 0. When it is not implemented,
requests can be ignored by the Modbus device.
Holding registers below 99 are reserved for legacy devices, and are optional. The functionality of
these registers is not changed or influenced by this specification.
Appendix B-5 Table 1: AM Managing Boiler Parameters
Bit 0: Write Enable, Bit 14:
Controller Reset
Bit0: °C / °F Bit1: bar / psi
1 = Managing / Stand-alone
Boiler
Depending on units °C / °F
Depending on units °C / °F
Depending on units °C / °F
Depending on units °C / °F
Depending on units °C / °F
Depending on units °C / °F
Heat exchanger temperature
Depending on units °C / °F
Depending on units 0..x bar/psi