42
JOHNSON CONTROLS
FORM 201.21-NM1 (616)
TECHNICAL DATA
WATER TEMPERATURE AND FLOWS
NOTES:
1. For leaving brine temperature below 40°F (4.4°C), contact your nearest YORK ofce for application requirements.
2. For leaving water temperature higher than 60°F (15.6°C), contact the nearest YORK ofce for application guidelines.
TEMPERATURE AND FLOWS
(ENGLISH UNITS)
MODEL
NUMBER
YCAV
LEAVING WATER
TEMPERATURE (F°)
COOLER FLOW
(GPM)
AIR ON
CONDENSOR (F°)
MIN.
1
MAX.
2
MIN. MAX. MIN. MAX.
0157 40 60 140 675 0 125
0177 40 60 160 750 0 125
0187 40 60 160 750 0 125
0197 40 60 160 750 0 125
0207 40 60 160 750 0 125
0227 40 60 160 750 0 125
0247 40 60 180 750 0 125
0267 40 60 180 800 0 125
NOTES:
1. For leaving brine temperature below 40°F (4.4°C), contact your nearest YORK ofce for application requirements.
2. For leaving water temperature higher than 60°F (15.6°C), contact the nearest YORK ofce for application guidelines.
TEMPERATURE AND FLOWS
(SI UNITS)
MODEL
NUMBER
YCAV
LEAVING WATER
TEMPERATURE (C°)
COOLER FLOW
(l/s)
AIR ON
CONDENSOR (C°)
MIN.
1
MAX.
2
MIN. MAX. MIN. MAX.
0157 4.4 15.6 8.8 42.6 -17.7 51.7
0177 4.4 15.6 10.1 47.3 -17.7 51.7
0187 4.4 15.6 10.1 47.3 -17.7 51.7
0197 4.4 15.6 10.1 47.3 -17.7 51.7
0207 4.4 15.6 10.1 47.3 -17.7 51.7
0227 4.4 15.6 11.4 47.3 -17.7 51.7
0247 4.4 15.6 11.4 47.3 -17.7 51.7
0267 4.4 15.6 11.4 50.5 -17.7 51.7