137JOHNSON CONTROLS
FORM NO.: 6U6K-B01E-NB-EN
TABLE 48 – WRITE DATA
BACNET POINT TABLE
Short Name
(BACnet Object Name)
Data
Type
Modify
IP Min
Value
IP
Max
Value
IP
Units
IP
Display
Prec
SI Min
Value
SI Max
Values
SI
Units
SI
Display
Prec
Enum Set
BACoid
(Customer BAS
BACnet)
Chiller On|Off (Command) Enum Yes None 1 None 1 0-Invalid, 1-On, 2-Off MV1
Running Mode Enum Yes None 1 None 1
0-Cooling, 1-Heat ing, 8-
Pump Circulation
MV2
Cool EWT Setpoint Float Yes 500 7 70 °F 0.1 100 250 °C 0.1 AV1
Heat EWT Setpoint Float Yes 5 90 1220 °F 0.1 150 500 °C 0.1 AV2
Cool LWT Setpoint Floa
t Yes 410 680 °F 0.1 50 200 °C 0.1 AV3
Heat LW T Setpoint Float Yes 680 1310 °F 0.1 200 550 °C 0.1 AV4
Noise Redu ction Boolean Yes None 1 None 1 BV1
Fault Restore Boolean Yes None 1 None 1 BV2
Cooling Control Select Enum Yes None 1 None 1
0-Manual EWT control,
1-Manual LWT control,
2-Auto LWT control
MV3
Heating Control Select Enum Yes None 1 None 1
0-Manual EWT control,
1-Manual LWT control,
2-Auto LWT control
MV4
Temp Control Cycle Float Yes 10 120 S 1 10 120 S 1 AV5
Water Temp Control Diff Fl
oat Yes 1 8 54 °F 0.1 10 30 °C 0 .1 AV6
EWT Pulldown Rate Select Unsigned Yes 0 6 None 1 0 6 None 1 AV7
Module Numb er Unsigned Yes 1 32 None 1 1 32 None 1 AV8