Jumps
165
1SVC 440 795 M0100
Power flow display
Jumped sections are indicated by the coils in the power flow
display.
All coils after the jump coil are shown with the symbol
:
of the jump coil.
Example
A selector switch allows two different sequences to be set.
Sequence 1: Switch on motor 1 immediately.
Sequence 2: Switch on Guard 2, wait time, then switch on
motor 1.
Contacts and relays used:
•I1 sequence 1
•I2 sequence 2
I3 guard 2 moved out
I12 motor-protective circuit-breaker switched on
Q1 motor 1
•Q2 guard 2
T1 wait time 30.00 s, on-delayed
D1 text “Motor-protective circuit-breaker tripped”
h
Attention!
If circuit connections are skipped, the states of the coils
are retained. The time value of timing relays that have
been started will continue to run.