Page #242 background image
Memory module
239
1SVC 440 795 M0100
Memory module The module is available as an accessory CL-LAS.MD003 for
CL-LSR/CL-LST and CL-LMR/CL-LMT.
Compatibility of memory modules MD001 and
MD002
Circuit diagrams with all the data can transferred to the
CL-LSR/CL-LST and CL-LMR/CL-LMT from the MD001 and
MD002 memory module. A transfer, however, in the other
direction is not possible.
Each memory module saves one CL circuit diagram.
Information stored on the memory module is “non-volatile”
and thus you can use the module to archive, transfer and
copy circuit diagrams.
The memory module can be used for saving
the circuit diagram
all parameter sets of the function relays
all display texts with functions
the system settings,
Input delay
P buttons
Password
Retention on/off,
•card start
summer time start/end time settings
X The memory module is fitted in the opened interface
provided for it.