Appendix
254
1SVC 440 795 M0100
Technical data General
CL…
CL-LEC.CI000
CL-LER.2O
CL-LSR,
CL-LST
CL-LMR,
CL-LMT
Dimensions W × H × D
[mm] 35.5 × 90 × 56.5 71.5 × 90 × 56.5 107.5 x 90 x 56.5
[inches] 1.4 × 3.54 × 2.08 2.81 × 3.54 × 2.08 4.23 × 3.54 × 2.08
Space units (SU) width 2 SU (space units)
wide
4 SU (space units)
wide
6 SU (space units)
wide
Weight
[g] 70 200 300
[lb] 0.154 0.441 0.661
Mounting Top-hat rail DIN 50022, 35 mm or screw mounting with 3 CL-LAS.FD001
fixing brackets (accessories); only 2 fixing brackets required for
CL-LEC.CI000 and CL-LER.2O.
Climatic environmental conditions
(Cold to IEC 60068-2-1, Heat to IEC 60068-2-2)
Ambient temperature during operation
Installed horizontally/vertically
–25 to 55 °C, –13 to 131 °F
Condensation
Prevent condensation with suitable measures
LCD display (reliably legible) 0 to 55 °C, 32 to 131 °F
Storage/transport temperature
–40 to +70 °C, –40 to 158 °F
Relative humidity (IEC 60068-2-30) 5 to 95 %, non-condensing
Air pressure (operation) 795 to 1080 hPa
Corrosion resistance
IEC 60068-2-42 SO
2
10 cm
3
/m
3
, 4 days
IEC 60068-2-43 H
2
S1 cm
3
/m
3
, 4 days
Inflammability class to UL 94 V 0
Ambient mechanical conditions
Pollution degree 2
Degree of protection (EN 50178, IEC 60529, VBG4) IP 20