EasyManuals Logo
Home>ABB>Relays>CL-LSR 12AC2 Series

ABB CL-LSR 12AC2 Series User Manual

ABB CL-LSR 12AC2 Series
296 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #154 background imageLoading...
Page #154 background image
Timing relays
151
1SVC 440 795 M0100
Timing relay modes
Time range
Variable values as time setpoint (I7, I8, I11, I12, actual value
T1 to T16, C1 to C16)
Parameters Switch function
X Switch with on-delay
?X Switch with on-delay and random time range
â Switch with off-delay
?â Switch with off-delay and random time range
Xâ On- and off-delayed, two time setpoints
?Xâ On- and off-delayed switching with random time, 2 time setpoints
ü Single-pulse switching
Ü Flash switching, mark-to-space ratio = 1:1, 2 time setpoints
Ü Flash switching, mark-to-space ratio k 1:1, 2 time setpoints
Parameters Time range and setpoint time Resolution
S 00.000 Seconds: 0.00 to 99.99 s 10 ms
M:S 00:00 Minutes: Seconds 00:00 to 99:59 1s
H:M 00:00 Hours: Minutes, 00:00 to 99:59 1 min.
h
Minimum time setting:
If a time value is less than the logic relay’s cycle time, the
elapsed time will not be recognised until the next cycle.
This may cause unforeseeable switching states.
h
If the value of the variable is greater than the maximum
permissible value of the configured time range, the
maximum value of the time range will be used as the
setpoint.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ABB CL-LSR 12AC2 Series and is the answer not in the manual?

ABB CL-LSR 12AC2 Series Specifications

General IconGeneral
BrandABB
ModelCL-LSR 12AC2 Series
CategoryRelays
LanguageEnglish

Related product manuals