CL-NET network, COM-LINK
serial connection
328
1SVC 440 795 M1100
REMOTE RUN å = Factory default setting
Configuring an input/output device (REMOTE IO)
All devices are factory set for operation as input and output
devices. This has the advantage that devices can be used
immediately as I/O devices, regardless of whether they have
a display or not. You only need to assign the station number.
This can be implemented via CL-SOFT or on a station 1 with
a display.
If you want to assign a device as an intelligent station on the
network, the REMOTE IO should be deactivated.
Figure: 183: Remote IO deactivated
Attention!
If several engineers are commissioning a machine or
system involving several spatially separated elements via
the CL-NET network, it must be ensured that REMOTE
RUN is not activated.
Otherwise unwanted machine or system starts may occur
during commissioning. The associated events depend on
the machines or systems involved.
REMOTE IO