CL-NET network, COM-LINK
serial connection
322
1SVC 440 795 M1100
Position and addressing of the operands via CL-NET
Sta-
tion
Display system Local expansion Network bit data Network word
data
Input Output Input Output Input Output Receive Send
I Q R S RN SN
1 1 I 1 to
16
1 Q 1 to 8 1 R 1 to
16
1 S 1 to 8 2 to 8 RN
1 to 32
2 to 8 SN
1 to 32
GT 1 to 32 PT 1 to
32
2 2 I 1
to 16
2 Q 1 to 8 2 R 1
to 16
2 S 1 to 8 1, 3 to 8
RN 1
to 32
1, 3 to 8
SN 1
to 32
GT 1 to 32 PT 1 to
32
3
3 I 1
to 16
3 Q 1 to 8 3 R 1
to 16
3 S 1 to 8 1, 2, 4 to
8 RN 1 to
32
1, 2, 4
to 8 SN 1
to 32
GT 1 to 32 PT 1 to
32
4
4 I 1
to 16
4 Q 1 to 8 4 R 1
to 16
4 S 1 to 8 1 to 3, 5
to 8 RN 1
to 32
1 to 3, 5
to 8 SN 1
to 32
GT 1 to 32 PT 1 to
32
5 5 I 1
to 16
5 Q 1 to 8 5 R 1
to 16
5 S 1 to 8 1 to 4, 6
to 8 RN 1
to 32
1 to 4, 6
to 8 SN 1
to 32
GT 1 to 32 PT 1 to
32
6
6 I 1
to 16
6 Q 1 to 8 6 R 1
to 16
6 S 1 to 8 1 to 5, 7,
8 RN 1 to
32
1 to 5, 7,
8 SN 1
to 32
GT 1 to 32 PT 1 to
32
7 7 I 1
to 16
7 Q 1 to 8 7 R 1
to 16
7 S 1 to 8 1 to 6, 8
RN 1
to 32
1 to 6, 8
SN 1
to 32
GT 1 to 32 PT 1 to
32
8
8 I 1
to 16
8 Q 1 to 8 8 R 1
to 16
8 S 1 to 8 1 to 7 RN
1 to 32
1 to 7
SN 1
to 32
GT 1 to 32 PT 1 to
32
h
The RN-SN connection is a point-to-point connection
between the defined stations. With RN and SN the number
of the contact must have the same number as the coil.
Example: 2SN30 from station 8 is sent to 8RN30 of station 2.