ï¿­ Diagnostic messages related to F-Parameters
If the FSPS-21 module encounters problems in processing the F-Parameters received from
the controller station (PLC), a diagnostic message is displayed. This may occur, for example,
when starting up the PROFINET communication between the controller station and the
module.
The table below includes a list of the diagnostic messages.
NotesDescriptionValue
(hex)
F_Dest_Add did not match the value con-
figured in the safety parameters (PROFIsafe.
11 PROFIsafe F_Dest_Add).
Mismatch of safety destination address
(F_Dest_Add).
64 (0x0040)
F_Dest_Add of 0 or FFFFh is not allowed.Safety destination address is not valid
(F_Dest_Add).
65
(0x0041) A valid F_Dest_Add is within range 1...65534.
F_Source_Add of 0 or FFFFh is not allowed.Safety source address is not valid
(F_Source_Add).
66
(0x0042) A valid F_Source_Add is within range
1...65534.
Watchdog time 0 ms is not allowed.Safety watchdog time value is 0 ms
(F_WD_Time).
67
(0x0043) A valid F_WD_Time is within range 1...65535.
F_SIL defined for this device at F-Host is not
correct. This device supports up to F_SIL = 3.
Parameter "F_SIL" exceeds SIL from specific
device application.
68
(0x0044)