What to doAUX code(s)DescriptionWarningCode
0000 000A Check PLC program
status.
PLC gave config
where fpar_crc does
not match to calcu-
lated one
If warning persists,
gather the AUX codes
from this fault and con-
tact ABB.
If warning persists,
gather the AUX codes
from this fault and con-
tact ABB.
0000 0010
Received new f-
parameters
Check PLC program
status.
0000 0011
Profisafe stack
stopped due to
profinet state
If warning persists,
gather the AUX codes
from this fault and con-
tact ABB.
Check PLC program
status.
0000 0012
Crc failure in cyclic
communication If warning persists,
gather the AUX codes
from this fault and con-
tact ABB.
Calculate a new watch-
dog time. See section
PROFIsafe response
time.
0000 0013
Watchdog timeout in
cyclic communica-
tion
If the warning reoccurs,
gather the AUX codes
from this fault and con-
tact ABB.
0000 0014
PLC set bit4 (activ-
ate_fv) in cyclic
communication
Event messages
DescriptionEventCode
FSX undefined event.FSx undefined event0xB795
If AUX = 0000 0000, no errors exist.FSx diagnostics0xB796
In any other case, gather the AUX codes from this event and contact
ABB.
LEDs
The adapter module is equipped with three bicolor diagnostic LEDs. The LEDs are described
below.
Fault tracing 183