NSOLL_A
Speed set point A
STW1
Control word 1
OUT area
NIST_A
Speed actual value A
ZSW1
Status word 1
IN area
ST2
PZD4PZD2...3PZD1
STW2
Control word 2
NSOLL_B
Speed set point B
STW1
Control word 1
OUT area
ZSW2
Status word 2
NIST_B
Speed actual value B
ZSW1
Status word 1
IN area
Note:
For the contents of the Control word, the Status word, references and actual values, see
chapter PROFINET IO – Communication profiles
■ Behavior of output data
ThenIf
Output data retains last valuesIOPS (PLC provider status)=Bad
Output data retains last valuesConnection loss
All output data is 0After power-up
Parameter handling using acyclic parameter access
mechanism (DP-V1)
PROFINET IO offers record read and write services for the acyclic parameter access
mechanism. When the drive parameters or FSPS-21 parameters are accessed, the
corresponding slot, sub-slot and index are set, and a PROFIdrive DP-V1 message is placed
on the data block of the record read or write frame.
■ Header and frame structures
PROFINET IO uses the DCE RPC (Distributed Computing Environment Remote Procedure
Call) protocol for acyclic read and write services. I/O controllers and supervisors take care
of formulating most of the request frames. However, it is possible that handling the
PROFIdrive request and response headers must be performed in the application logic. The
acyclic frame structure, headers and error codes are described further below.
DataRead or
Write
NDRRPCIP UDPEther
type
Src addr.Dest ad-
dr.
Frames
…64208028266Bytes
Dest addr. and Src addr. are the destination and the source of the communication
relationship. The addresses are in hexadecimal format, for example, 00-30-11-02-57-AD.
Ether type is 0x800 for non-real-time communication.
90 PROFINET IO – Communication protocol