46 PROFINET IO – Communication profiles
The figure below illustrates the profile selection:
Note: The diagram is applicable only when PPO messaging is used. If
Standard Telegrams (ST) are used, the communication profile is selected
automatically.
The following sections describe the Control word, the Status word,
references and actual values for the PROFIdrive and ABB Drives
communication profiles. Refer to the drive manuals for details on
the native profiles.
Drive
Profile selection:
Data conversion
Data conversion
PROFIdrive
ABB Drives
Transparent32
1)
Native profile (eg, DCU or FBA)
Optional
reference/actual
value scaling
Transparent16
Select
Group A
Par. 02
Data conversion
PROFIdrive
positioning
PROFINET
CW
REF1
REF2
SW
ACT1
ACT2
16/32
-bit
Select
Group A
Par. 02
PROFINET
PZDx
•
•
•
•
PZD10
1)
1)
1)
16/32
-bit
Profile_selection.pdf
Note:
The diagram is applicable only when PPO messaging is used. If Standard Telegrams (ST)
are used, the communication profile is selected automatically.
The following sections describe the Control word, the Status word, references and actual
values for the PROFIdrive and ABB Drives communication profiles. Refer to the drive
manuals for details on the native profiles.
PROFIdrive communication profile
■ Control word and Status word
The Control word (PROFIdrive parameter 967) is the principal means for controlling the
drive from a fieldbus system. It is sent by the fieldbus master station to the drive through
the adapter module. The drive switches between its states according to the bit-coded
instructions in the Control word and returns status information to the master in the Status
word (PROFIdrive parameter 968).
The contents of the Control word and the Status word are detailed below. See the drive
documentation for information on the drive-specific bits. The drive states are presented on
page 78. The drive states for the positioning mode are presented on page 78.
74 PROFINET IO – Communication profiles