EasyManuals Logo

ABB FSPS-21 User Manual

ABB FSPS-21
214 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #96 background imageLoading...
Page #96 background image
Used atMeaningError #
Access to an unavailable description (parameter value
is available)
No description data available09h
Change access rights without rights to change para-
meters
No operation priority0Bh
Access to a text array that is not available (Parameter
value is available.)
No text array available0Fh
Access is temporarily not possible for reasons that are
not specified in detail.
Request cannot be executed because of
operating mode
11h
Change access with a value that is within limits but is
not permissible for other long-term reasons (parameter
with defined single values)
Value impermissible14h
The length of the current response exceeds the max-
imum transmittable length.
Response too long15h
Illegal value or value that is not supported for the attrib-
ute, number of elements, parameter number or sub-
index, or a combination
Parameter address impermissible16h
Write request: Illegal format or format of parameter
data that is not supported
Illegal format17h
Write request: Number of values of the parameter data
does not match the number of elements at the paramet-
er address.
Number of values inconsistent18h
Manufacturer-specific error area65h
FF
Vendor-specific errorVendor-specific error65h
Request not supportedRequest not supported66h
Request cannot be completed because of a communic-
ation error.
Communication error67h
Failure during write to non-volatile memoryNon-volatile error6Eh
Request aborted because of a timeout.Time-out error6Fh
Parameter cannot be mapped to PZD (size mismatch
or non-existent).
PZD map failure78h
Parameter cannot be mapped to PZD (out of memory).PZD memory failure79h
Parameter cannot be mapped to PZD (multiple PZD
write).
Multiple PZD map7Ah
Cannot map Control word bit (parameter 933…937,
e.g., double mapping of bits).
Control word bit map82h
Cannot change mode to TORQUE (frequency is used).Set torque mode error8Ch
The request ID of the response is illegal.Illegal Request ID90h
Buffer overflowInternal buffer96h
Communication error between the module and the
drive
Internal communicationA0h
96 PROFINET IO Communication protocol

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ABB FSPS-21 and is the answer not in the manual?

ABB FSPS-21 Specifications

General IconGeneral
BrandABB
ModelFSPS-21
CategoryControl Unit
LanguageEnglish