analog output channel, it cannot be connected to another physical analog output
channel.
3. Click the Save button on the toolbar to save the connection changes.
5.3.5 Connecting GOOSE receive signals
The GOOSE receive input signals are those signals that are communicated to one IED
from another IED using the IEC 61850 GOOSE communication mechanism.
1. Click the GOOSE tab in the tool window.
The availability and the appearance of the grid depend on the IED.
2. Create or delete connections between GOOSE receive signals and input signals.
• Double-click an empty cell to create a connection.
• Double-click a cell with a symbol X to delete a connection.
The Signal Matrix connection rules prevent incompatible connections.
Incompatible connection cells are disabled and shown in red.
3. Click the Save button on the toolbar to save the connection changes.
5.4 Using Ethernet Configuration
Ethernet Configuration is used to configure the Ethernet ports both online and offline.
The Ethernet configuration can be started using the shortcut menu in the plant
structure or from the PCM600 main menu.
1. In Plant Structure, select an IED.
2. Select Ethernet Configuration in one of the alternative ways.
• Right-click any IED in the PCM600 object tree and select Ethernet
Configuration from the shortcut menu list.
• On the Tools menu, select Ethernet Configuration.
3. Use the tabs to configure the access points, merging unit and routers.
1MRS757866 C Section 5
Use cases for engineering and commissioning
PCM600 51
Getting Started Guide