11.3.2 Protective device compliance (North America)
Requirements Specifications
Dedicated upstream protection device(s) Breaker
EVSE internal Ground Fault Protection 20mA AC
Upstream overcurrent protection breaker
Note: The breaker value de-
pends on the diameter and the
length of the cable, the EVSE
rating, and the environmental
parameters (for the electrician
to decide).
The breaker serves as the main disconnect
switch to the EVSE.
Breaker rating:
• 40A for a 32 Amp rated EVSE
• 20A for a 16 Amp rated EVSE
11.4 Parts included in the delivery
Parameter Specification
EVSE Refer to the type plate. Refer to section
2.3
.
Upper mounting screws M6 x 60
Plugs for the upper mounting screws (servi-
cable for a brick wall)
8 x 60 mm
Lower mounting screws M6 x 120
Plugs for the lower mounting screws (servi-
cable for a brick wall)
10 x 60 mm
Installation template -
RFID card MIFARE
11.5 General specifications
Parameter Specification
Compliance and safety
• IEC/EN 61851-1
• IEC/EN 62311
• IEC/UL 62479
• IEC/UL 62955 TüV listed conforming to
UL 2594, UL 2231-1, UL 2231-2, UL 1998
• CSA C22.2. NO.280
Certification CE, MiD, TüV, Energy Star
IP rating The type plate shows the specification. Refer
to section
2.3
.
Technical data
BCM.V3Y01.0-EN | 001 47