Parameter Specification [mm] Specification [inches]
Z1 > 200 > 8
Z2 (indoor use) > 457.2 > 18
Z2 (outdoor use) > 635 > 25
11.11 AC input specifications
11.11.1 General specifications
Parameter Specification
Earthing systems TT
TN-S
TN-C-S
IT
Frequency 50 Hz or 60 Hz
Overvoltage category Category III
Protection Overcurrent
Overvoltage
Undervoltage
Earth fault, including DC leakage protection
Integrated surge protection
11.11.2 400 VAC 3-phase with neutral (TT, TN) (Europe)
Phase A
PE
Neutral (N)
Phase B
Phase C
L1 N L2 L3
U1
U2
U1 230 VAC, maximum 264 VAC U2 400 VAC, maximum 460 VAC
Technical data