Setup menu
- DHW SETUP procedures
The fi rst window of the DHW SETUP allows the installer to
set the number of units producing domestic hot water; this
window displays the following information:
- Number of units to produce DHW (
1
): indicates which
units will be used to produce domestic hot water; this
parameter also includes any reserve units (if the relative
parameter specifi es their presence: Setup menu - SYSTEM
SETUP procedures - Presence of reserve chiller).
From this window it is possible to:
(1) Set the number of units for DHW production: pressing the
key
C
will allow you to enter the modifi cation mode and the value
will be highlighted; by pressing the keys
A
or
B
it will be possible
to modify the value currently displayed, while pressing the key
C
will confi rm this choice.
(2) Pass on to the next window:
to go to the next window of this menu, press the key
B
.
(3) Exit this window:
press the key
A
to return to the selection of the SETUP menus.
(4) Exit this window:
press the key
D
to return to the selection of the USER menus.
• Setting number of units for DHW production (Password 303):
ATTENTION: to correctly set management of units for DHW production, the following guidelines must be
respected:
(1) Modbus address of units: the units must have a specifi c modbus address to be able to be managed properly
by the MULTI CONTROL accessory; this address can only be set from the panel on the unit (for further information
on procedures for setting a serial address on the units, refer to its user manual); the addresses to be set on the
units depend on the number and function which the units perform in the system; to clarify which are the correct
addresses to be applied to the units for DHW production, see the summary table on the next page.
(2) Type of unit: if the system is provided with a reserve chiller, this unit will be the one with the highest modbus
address (as indicated in the summary table on the next page); moreover, if the system envisions the both
possibility of a reserve chiller and DHW production enabling, ALL the units of the system must be capable of
producing domestic hot water (therefore they must all be heat pumps or heating only units).
A
B
C
ESC
D
DHW units
2
1
DHW units
2

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the AERMEC MULTI CONTROL and is the answer not in the manual?

AERMEC MULTI CONTROL Specifications

General IconGeneral
BrandAERMEC
ModelMULTI CONTROL
CategoryControl Panel
LanguageEnglish

Related product manuals