The sixth window of the PLANT SETUP allows the user to
set the temperature at which to deactivate each unit (a
switch-off value is set for each unit) if the installer has set
the management logic according to DELTA T; this window
displays the following information:
- Unit currently selected (
1
): indicates which unit is
currently selected which the displayed data refers to.
- Unit deactivation setting (
2
): indicates the temperature (at
the SIW probe) of the water returning from the primary circuit
considered the deactivation threshold of the corresponding
unit
(depending on the season, the demand will be activated
above or below the threshold set in this parameter).
- Unit activation setting season (
3
): indicates which
season the temperature setting currently displayed refers to.
From this window it is possible to:
(1) Select a unit for which to set switch-off: pressing the keys
D
or
E
decreases or increases the index which indicates
which unit the work setting currently displayed refers to (
1
);
remember that each unit can be set with different deactivation
settings
.
(2) Set a temperature to switch the units off during DELTA T
mode: pressing the key
C
will allow you to enter the modifi cation
mode and the
current deactivation setting will be highlighted (
2
);
by pressing the keys
A
or
B
it will be possible to modify the
value currently displayed, while pressing the key
C
will confi rm
this choice.
(3) Select heating or cooling setting: by pressing the key
D
you will switch from viewing the cooling setting ( ) to the heating
setting ( ).
(4) Go back to the previous window:
to go back to the previous window of this menu, press the
key
A
.
(5) Exit this window:
press the key
E
to return to the selection of the USER menus.
• Setting deactivation with DELTA T control (Password 101 or 303):
Deactivation logic with DELTA T control
Off On OffUnit (1)
Off On OffUnit (1)
Off On OffUnit (1)
Off On OffUnit (1)
Temperature
SIW
Temperature
SUW
A
B
C
ESC
G
OFF temperature
+40.0
o
C
2
F
3
N:1
E D
OFF temperature
+40.0
o
C
N:1
1

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the AERMEC MULTI CONTROL and is the answer not in the manual?

AERMEC MULTI CONTROL Specifications

General IconGeneral
BrandAERMEC
ModelMULTI CONTROL
CategoryControl Panel
LanguageEnglish

Related product manuals