Setup menu
- PLANT SETUP procedures
The fi rst window of the PLANT SETUP allows the installer to
set the number of units connected to MULTI CONTROL; this
window displays the following information:
- Number of units installed in plant (
1
): indicates how
many units will be managed by MULTI CONTROL.
From this window it is possible to:
(1) Set the number of units of the plant: pressing the key
C
will allow you to enter the modifi cation mode and the value will be
highlighted; by pressing the keys
A
or
B
it will be possible to
modify the value currently displayed, while pressing the key
C
will confi rm this choice.
(2) Pass on to the next window:
to go to the next window of this menu, press the key
B
.
(3) Exit this window:
press the key
A
to return to the selection of the SETUP menus.
(4) Exit this window:
press the key
D
to return to the selection of the USER menus.
• Setting the number of units installed (Password 303):
ATTENTION: to correctly set management of the units by the MULTI CONTROL accessory, they must have
a correctly set serial address; the values with which the units must be set are:
Unit number 1 = Modbus Address 200.
Unit number 2 = Modbus Address 201.
Unit number 3 = Modbus Address 202.
Unit number 4 = Modbus Address 203.
A
B
C
ESC
D
Number of units
2
1
Numeber of units
2