EasyManuals Logo
Home>AERMEC>Control Panel>MULTI CONTROL

AERMEC MULTI CONTROL User Manual

AERMEC MULTI CONTROL
64 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #37 background imageLoading...
Page #37 background image
37
4598010_00
GB
Number of
units for
DHW
Type of system
Modbus serial addresses
(1)
1 2 3 4
1
1
DHW storage tank
200 / / /
2
1 2
DHW storage tank
200 201 / /
3
1 2 3
DHW storage tank
200 201 202 /
4
1 2 3 4
DHW storage tank
200 201 202 203
Modbus addresses for units for DHW production (without reserve chiller):
Type of systems for DHW production:
The fi rst three types of systems have one or more units for DHW production, however they can have other COOLING ONLY
chillers for the system (MULTI CONTROL manages a maximum of 4 units); in this case, it is MANDATORY that the units used for
production of domestic hot water be set with the addresses specifi ed in this table and that eventual cooling only chillers be set
with the serial addresses remaining available.
Remember that to identify the units managed by MULTI CONTROL, the addresses available are:
Unit number 1 = Modbus Address 200.
Unit number 2 = Modbus Address 201.
Unit number 3 = Modbus Address 202.
Unit number 4 = Modbus Address 203.
(1)
The Modbus serial addresses must be set on the units by means of their on-board control panel.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the AERMEC MULTI CONTROL and is the answer not in the manual?

AERMEC MULTI CONTROL Specifications

General IconGeneral
BrandAERMEC
ModelMULTI CONTROL
CategoryControl Panel
LanguageEnglish

Related product manuals