47
4598010_00
GB
39 R 200 700
1
/
10
°C Yes No No
Heating switch-off temperature of first unit during
"Delta T Control" functioning
40 R -100 300
1
/
10
°C Yes No No
Cooling switch-off temperature of second unit during
"Delta T Control" functioning
41 R 200 700
1
/
10
°C Yes No No
Heating switch-off temperature of second unit during
"Delta T Control" functioning
42 R -100 300
1
/
10
°C Yes No No
Cooling switch-off temperature of third unit during
"Delta T Control" functioning
43 R 200 700
1
/
10
°C Yes No No
Heating switch-off temperature of third unit during
"Delta T Control" functioning
44 R -100 300
1
/
10
°C Yes No No
Cooling switch-off temperature of fourth unit during
"Delta T Control" functioning
45 R 200 700
1
/
10
°C Yes No No
Heating switch-off temperature of fourth unit during
"Delta T Control" functioning
46 R -200 700
1
/
10
°C Yes No No
External air temperature threshold Px1 during summer
mode
47 R -200 700
1
/
10
°C Yes No No
Water outlet temperature threshold Py1 during
summer mode
48 R -200 700
1
/
10
°C Yes No No
External air temperature threshold Px2 during summer
mode
49 R -200 700
1
/
10
°C Yes No No
Water outlet temperature threshold Py2 during
summer mode
50 R -200 700
1
/
10
°C Yes No No
External air temperature threshold Px1 during winter
mode
51 R -200 700
1
/
10
°C Yes No No
Water outlet temperature threshold Py1 during winter
mode
52 R -200 700
1
/
10
°C Yes No No
External air temperature threshold Px2 during winter
mode
53 R -200 700
1
/
10
°C Yes No No
Water outlet temperature threshold Py2 during winter
mode
54 R 0 1 // Yes No No Climatic curve enabling
55 R 0 2 // Yes No No Unit 1 type
56 R 0 2 // Yes No No Unit 2 type
57 R 0 2 // Yes No No Unit 3 type
58 R 0 2 // Yes No No Unit 4 type
59 R 0 4 // Yes No No Number of units for domestic hot water production
60 R 0 1 // Yes No No Simultaneous loads
61 R 0 60 m Yes No No RAS switch-on delay
62 R 0 120 s Yes No No Valve rotation time
63 R 20 100
1
/
10
°C Yes No No DHW mode setting band
64 R 0 50
1
/
10
°C Yes No No DHW mode setting delta
65 R 0 1 // Yes No No Type of defrosting
66 R 0 2 // Yes No No Remote control enabling
67 R 0 3 // Yes No No Baud rate
68 R 0 200 // Yes No No Address
69 R 0 1 // Yes No No Presence of expansion module 1
70 R 0 1 // Yes No No Presence of expansion module 2
71 R 0 1 // Yes No No Presence of expansion module 3
100 W 0 1 // Yes Yes No Force reset of units in system