Publication 1747-UM006B-EN-P - June 2003
6-6 Start-Up and Operation
Remote Expansion Chassis
Power Loss
If power to any remote expansion chassis is lost, a 1747-ASB module
error occurs. When power to the remote expansion chassis is
restored, the 1747-ASB module acts as if its own chassis power was
cycled and resets itself, restoring normal operation unless a major fault
occurred.
The 1747-ASB module assigns each slot in the remote chassis and
remote expansion chassis a fixed amount of its image using slot
addressing. The 1747-ASB module then maps the I/O module's
images to the portion of the 1747-ASB image that is assigned to their
slots.
Invalid RIO Link Transfers
If the I/O module in any slot is block transfer mapped, the 1747-ASB
module expects data for that I/O module to be transferred on the RIO
link using RIO block transfers. If the I/O module in any slot is
discretely mapped, the 1747-ASB expects data for that I/O module to
be transferred on the RIO link using RIO discrete transfers.
An Invalid RIO link transfer occurs when the 1747-ASB module
receives data for a slot in a manner other than that for which the
1747-ASB module is expecting to receive data for that slot.
Invalid RIO link transfers are categorized below. Errors are not
generated by these conditions:
RIO discrete or block transfers to empty or nonexistent slots
RIO discrete transfers to block transfer slots
RIO block transfers to discrete slots
invalid length RIO block transfers
RIO Discrete or Block Transfers To Empty or Nonexistent Chassis
Slots
Discrete output image data received by the 1747-ASB module or RIO
block transfers to empty or nonexistent slots are ignored by the
1747-ASB module.
Discrete input image data sent by the 1747-ASB module for empty or
nonexistent slots are all zeros.
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com

Table of Contents

Other manuals for Allen-Bradley 1747-ASB

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Allen-Bradley 1747-ASB and is the answer not in the manual?

Allen-Bradley 1747-ASB Specifications

General IconGeneral
BrandAllen-Bradley
Model1747-ASB
CategoryControl Unit
LanguageEnglish

Related product manuals