Rockwell Automation Publication 22C-UM001J-EN-E - January 2017 67
Programming and Parameters Chapter 3
T055 [Relay Out1 Sel] Related Parameter(s): P033
, T056, T058, T059, T069, T072, T073, T076, A163, d318
Sets the condition that changes the state of the output relay contacts.
Options 0 “Ready/Fault” (Default) Relay changes state when power is applied. This indicates that the drive is ready for operation. Relay returns drive to shelf state
when power is removed or a fault occurs.
1 At Frequency Drive reaches commanded frequency
2 “MotorRunning” Motor is receiving power from the drive.
3 “Hand Active Active when drive is in local control.
4 “Motor Overld Motor overload condition exists.
5 “Ramp Reg” Ramp regulator is modifying the programmed accel/decel times to avoid an overcurrent or overvoltage fault from occurring.
6 Above Freq” Drive exceeds the frequency (Hz) value set in T056
[Relay Out1 Level].
Use T056 to set threshold.
7 Above Cur” Drive exceeds the current (% Amps) value set in T056
[Relay Out1 Level].
Use T056 to set threshold.
8 Above DCVolt” Drive exceeds the DC bus voltage value set in T056
[Relay Out1 Level].
• Use T056 to set threshold.
9 Above Anlg 2” Analog input voltage (I/O Terminal 17) exceeds the value set in T056
[Relay Out1 Level].
Do not use if T073 [Analog In 2 Sel] is set to 3 “Voltage Mode - Bipolar”.
This parameter setting can also be used to indicate a PTC trip point when the input (I/O Terminal 17) is wired to a PTC and
external resistor.
Use T056 to set threshold.
10 Above PF Ang Power Factor angle has exceeded the value set in T056 [Relay Out1 Level].
Use T056 to set threshold.
11 Anlg In Loss” Analog input loss has occurred. Program T072
[Analog In 1 Loss] and/or T076 [Analog In 2 Loss] for desired action when input
loss occurs.
12 “ParamControl” Enables the output to be controlled over network communications by writing to T056
[Relay Out1 Level]. (0 = Off, 1 = On.)
13 “Retries Exst” Value set in A163 [Auto Rstrt Tries] is exceeded.
14 “NonRec Fault” Number of retries for A163
[Auto Rstrt Tries] is exceeded, or
Non-resettable fault occurs, or
A163 [Auto Rstrt Tries] is not enabled.
15 “Reverse” Drive is commanded to run in reverse direction.
16 “Logic In 1” An input is programmed as “Logic In 1” and is active.
17 “Logic In 2” An input is programmed as “Logic In 2” and is active.
23 Aux Motor Auxiliary Motor is commanded to run. Refer to Appendix C
for details.
24 “Fault” (with FRN 7.xx and later) Relay remains in the off state when power is applied to the drive and energizes when a fault occurs. This is inverted from Option
0, “Ready/Fault.
IMPORTANT
Value for T056 [Relay Out1 Level] must be entered in percent of drive rated output current.
T056 [Relay Out1 Level] Related Parameter(s): T055, T058, T059, d318
32 bit parameter.
Sets the trip point for the digital output relay if the value of T055 [Relay Out1 Sel] is 6, 7, 8, 9, 10 or 12.
Values Default: 0.0
Min/Max: 0.0/9999
Display: 0.1
32
T055 Setting T056 Min/Max
6 0/320 Hz
7 0/180%
8 0/815 Volts
9 0/100%
10 1/180 degs
12 0/1

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Allen-Bradley 22C-D038A103 and is the answer not in the manual?

Allen-Bradley 22C-D038A103 Specifications

General IconGeneral
BrandAllen-Bradley
Model22C-D038A103
CategoryController
LanguageEnglish

Related product manuals