Rockwell Automation Publication 22C-UM001J-EN-E - January 2017 71
Programming and Parameters Chapter 3
T068 [Opto Out Logic] Related Parameter(s): T065
, T066
Determines the logic (Normally Open/NO or Normally Closed/NC) of the opto output.
.
Note: Setting output to NC may cause output to “glitch” on power-up. The off/reset state of all outputs is open.
Values Default: 0
Min/Max: 0/1
Display: 1
T058 Option Opto Out Logic
0 NO (Normally Open)
1 NC (Normally Closed)
T069 [Analog In 1 Sel] Related Parameter(s): T055, T070, T071, T072
Sets the analog input signal mode (0-20mA, 4-20mA, or 0-10V). This parameter must match DIP Switch AI1 setting on the control board.
.
Values Default: 2
Min/Max: 0/6
Display: 1
T069 Option Setting Input Range DIP Switch AI1 Setting
0 Current Mode 0-20 mA 20 mA
1 Current Mode 4-20 mA 20 mA
2 Voltage Mode - Unipolar 0-10V 10V
4 Current Mode (Square Root) 0-20 mA 20 mA
5 Current Mode (Square Root) 4-20 mA 20 mA
6 Voltage Mode - Unipolar (Square Root) 0-10V 10V
T070 [Analog In 1 Lo] Related Parameter(s): P034, P038, T069, T071, T072, A152, A153
Stop drive before changing this parameter.
Sets the analog input level that corresponds to P034 [Minimum Freq].
Analog inversion can be accomplished by setting this value larger than T071
[Analog In 1 Hi].
Values Default: 0.0%
Min/Max: 0.0/100.0%
Display: 0.1%
IMPORTANT
If analog inversion is implemented the drive will go to maximum frequency in the event the analog input is lost. It is strongly recommended to activate
T072 [Analog In 1 Loss] to protect from this potential occurrence.
0
P035 [Maximum Freq]
P034 [Minimum Freq]
T070 [Analog In 1 Lo] T071 [Analog In 1 Hi]
0
Speed Reference
T071 [Analog In 1 Hi] Related Parameter(s): P035, P038, T069, T070, T072, A152, A153
Stop drive before changing this parameter.
Sets the analog input level that corresponds to P035 [Maximum Freq].
Analog inversion can be accomplished by setting this value smaller than T070
[Analog In 1 Lo].
Values Default: 100.0%
Min/Max: 0.0/100.0%
Display: 0.1%

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Allen-Bradley 22C-D038A103 and is the answer not in the manual?

Allen-Bradley 22C-D038A103 Specifications

General IconGeneral
BrandAllen-Bradley
Model22C-D038A103
CategoryController
LanguageEnglish

Related product manuals