70 Rockwell Automation Publication 22C-UM001J-EN-E - January 2017
Chapter 3 Programming and Parameters
T065 [Opto Out Sel] Related Parameter(s): P033
, T066, T068, T072, T076, A163, d318
Determines the operation of the programmable opto output.
Options 0 “Ready/Fault” Opto output is active when power is applied. This indicates that the drive is ready for operation. Opto output is inactive when
power is removed or a fault occurs.
1 At Frequency” (Default) Drive reaches commanded frequency
2 “MotorRunning” Motor is receiving power from the drive.
3 “Hand Active Active when drive is in local control.
4 “Motor Overld Motor overload condition exists.
5 “Ramp Reg” Ramp regulator is modifying the programmed accel/decel times to avoid an overcurrent or overvoltage fault from occurring.
6 Above Freq” Drive exceeds the frequency (Hz) value set in T066
[Opto Out Level].
Use T066 to set threshold.
7 Above Cur” Drive exceeds the current (% Amps) value set in T066
[Opto Out Level].
Use T066 to set threshold.
8 Above DCVolt” Drive exceeds the DC bus voltage value set in T066
[Opto Out Level].
• Use T066 to set threshold.
9 Above Anlg 2” Analog input voltage (I/O Terminal 17) exceeds the value set in T066
[Opto Out Level].
Do not use if T073 [Analog In 2 Sel] is set to 3 “Voltage Mode - Bipolar”.
This parameter setting can also be used to indicate a PTC trip point when the input (I/O Terminal 17) is wired to a PTC and
external resistor.
Use T066 to set threshold.
10 Above PF Ang Power Factor angle has exceeded the value set in T066 [Opto Out Level].
Use T066 to set threshold.
11 Anlg In Loss” Analog input loss has occurred. Program T072
[Analog In 1 Loss] and/or T076 [Analog In 2 Loss] for desired action when input
loss occurs.
12 “ParamControl” Enables the output to be controlled over network communications by writing to T066
[Opto Out Level]. (0 = Off, 1 = On.)
13 “Retries Exst” Value set in A163 [Auto Rstrt Tries] is exceeded.
14 “NonRec Fault” Number of retries for A163
[Auto Rstrt Tries] is exceeded, or
Non-resettable fault occurs, or
A163 [Auto Rstrt Tries] is not enabled.
15 “Reverse” Drive is commanded to run in reverse direction.
16 “Logic In 1” An input is programmed as “Logic In 1” and is active.
17 “Logic In 2” An input is programmed as “Logic In 2” and is active.
24 “Fault” (with FRN 7.xx and later) Relay remains in the off state when power is applied to the drive and energizes when a fault occurs. This is inverted from Option
0, “Ready/Fault.
IMPORTANT
Value for T066 [Opto Out Level] must be entered in percent of drive rated output current.
T066 [Opto Out Level] Related Parameter(s): T065, T068, A163, d318
32 bit parameter.
Determines the on/off point for the opto output when T065 [Opto Out Sel] is set to option 6, 7, 8, 9, 10,or 12.
.
Values Default: 0.0
Min/Max: 0.0/9999
Display: 0.1
32
T065 Setting T066 Min/Max
6 0/320 Hz
70/180%
80/815 Volts
90/100%
10 1/180 degs
12 0/1

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Allen-Bradley 22C-D038A103 and is the answer not in the manual?

Allen-Bradley 22C-D038A103 Specifications

General IconGeneral
BrandAllen-Bradley
Model22C-D038A103
CategoryController
LanguageEnglish

Related product manuals