Setting Output Range Minimum Output Value Maximum Output Value =
[Analog Output High]
Filter
(1)
(1) For settings with the filter enabled, if a 0-100% step change occurs, the output will reach 95% in 500 milliseconds, 99% in 810 milliseconds and 100% in 910 milliseconds.
DIP Switch
AO1 Setting
Related
Parameter
0 OutFreq 0-10 0-10V 0V = 0 Hz [Maximum Freq] None 10V b001
1 OutCurr 0-10 0-10V 0V = 0 Amps 200% Drive Rated FLA Filter A 10V b003
2 OutTorq 0-10 0-10V 0V = 0 Amps 200% Drive Rated FLA Filter A 10V b013
3 OutVolt 0-10 0-10V 0V = 0 Volts 120% Drive Rated Output V None 10V b004
4 OutPowr 0-10 0-10V 0V = 0 kW 200% Drive Rated Power Filter A 10V b010
5 Setpnt 0-10 0-10V 0V = 0.0% 100.0% Setting None 10V T084
6 TstData 0-10 0-10V 0V = 0000 65535 (Hex FFFF) None 10V A196
7 OutFreq 0-20 0-20 mA 0 mA = 0 Hz [Maximum Freq] None 20 mA b001
8 OutCurr 0-20 0-20 mA 0 mA = 0 Amps 200% Drive Rated FLA Filter A 20 mA b003
9 OutTorq 0-20 0-20 mA 0 mA = 0 Amps 200% Drive Rated FLA Filter A 20 mA b013
10 OutVolt 0-20 0-20 mA 0 mA = 0 Volts 120% Drive Rated Output V None 20 mA b004
11 OutPowr 0-20 0-20 mA 0 mA = 0 kW 200% Drive Rated Power Filter A 20 mA b010
12 Setpnt 0-20 0-20 mA 0 mA = 0.0% 100.0% Setting None 20 mA T084
13 TstData 0-20 0-20 mA 0 mA = 0000 65535 (Hex FFFF) None 20 mA A196
14 OutFreq 4-20 4-20 mA 4 mA = 0 Hz [Maximum Freq] None 20 mA b001
15 OutCurr 4-20 4-20 mA 4 mA = 0 Amps 200% Drive Rated FLA Filter A 20 mA b003
16 OutTorq 4-20 4-20 mA 4 mA = 0 Amps 200% Drive Rated FLA Filter A 20 mA b013
17 OutVolt 4-20 4-20 mA 4 mA = 0 Volts 120% Drive Rated Output V None 20 mA b004
18 OutPowr 4-20 4-20 mA 4 mA = 0 kW 200% Drive Rated Power Filter A 20 mA b010
19 Setpnt 4-20 4-20 mA 4 mA = 0.0% 100.0% Setting None 20 mA T084
20 TstData 4-20 4-20 mA 4 mA = 0000 65535 (Hex FFFF) None 20 mA A196
21 MinFreq 0-10 0-10V 0V = Min. Freq [Maximum Freq] None 10V b001
22 MinFreq 0-20 0-20 mA 0 mA = Min. Freq [Maximum Freq] None 20 mA b001
23 MinFreq 4-20 4-20 mA 4 mA = Min. Freq [Maximum Freq] None 20 mA b001
24 AnlgIn1 0-10 0-10V 0V = 0.0% 100.0% Setting Filter A 10V d305
25 AnlgIn1 0-20 0-20 mA 0 mA = 0.0% 100.0% Setting Filter A 20 mA d305
26 AnlgIn1 4-20 4-20 mA 4 mA = 0.0% 100.0% Setting Filter A 20 mA d305
27 AnlgIn2 0-10 0-10V 0V = 0.0% 100.0% Setting Filter A 10V d306
28 AnlgIn2 0-20 0-20 mA 0 mA = 0.0% 100.0% Setting Filter A 20 mA d306
29 AnlgIn2 4-20 4-20 mA 4 mA = 0.0% 100.0% Setting Filter A 20 mA d306
.