EasyManuals Logo
Home>Allen-Bradley>Controller>22C-D038A103

Allen-Bradley 22C-D038A103 User Manual

Allen-Bradley 22C-D038A103
196 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #78 background imageLoading...
Page #78 background image
76 Rockwell Automation Publication 22C-UM001J-EN-E - January 2017
Chapter 3 Programming and Parameters
T084 [Anlg Out1 Setpt] Related Parameter(s): T082
, T083
Sets direct parameter control over the analog output. If enabled, this sets the percent value of analog output.
Values Default: 0.0%
Min/Max: 0.0/100.0%
Display: 0.1%
T085 [Analog Out2 Sel] Related Parameter(s): P035, T086, T087
Sets the analog output signal mode (0-20 mA, 4-20 mA, or 0-10V). The output is used to provide a signal that is proportional to several drive conditions. This parameter must match
DIP Switch AO2 setting.
Values Default: 1
Min/Max: 0/29
Display: 1
Setting Output Range Minimum Output Value Maximum Output Value =
[Analog Output High]
Filter
(1)
(1) For settings with the filter enabled, if a 0-100% step change occurs, the output will reach 95% in 500 milliseconds, 99% in 810 milliseconds and 100% in 910 milliseconds.
DIP Switch
AO2 Setting
Related
Parameter
0 OutFreq 0-10 0-10V 0V = 0 Hz [Maximum Freq] None 10V b001
1 OutCurr 0-10 0-10V 0V = 0 Amps 200% Drive Rated FLA Filter A 10V b003
2 OutTorq 0-10 0-10V 0V = 0 Amps 200% Drive Rated FLA Filter A 10V b013
3 OutVolt 0-10 0-10V 0V = 0 Volts 120% Drive Rated Output V None 10V b004
4 OutPowr 0-10 0-10V 0V = 0 kW 200% Drive Rated Power Filter A 10V b010
5 Setpnt 0-10 0-10V 0V = 0.0% 100.0% Setting None 10V T084
6 TstData 0-10 0-10V 0V = 0000 65535 (Hex FFFF) None 10V A196
7 OutFreq 0-20 0-20 mA 0 mA = 0 Hz [Maximum Freq] None 20 mA b001
8 OutCurr 0-20 0-20 mA 0 mA = 0 Amps 200% Drive Rated FLA Filter A 20 mA b003
9 OutTorq 0-20 0-20 mA 0 mA = 0 Amps 200% Drive Rated FLA Filter A 20 mA b013
10 OutVolt 0-20 0-20 mA 0 mA = 0 Volts 120% Drive Rated Output V None 20 mA b004
11 OutPowr 0-20 0-20 mA 0 mA = 0 kW 200% Drive Rated Power Filter A 20 mA b010
12 Setpnt 0-20 0-20 mA 0 mA = 0.0% 100.0% Setting None 20 mA T084
13 TstData 0-20 0-20 mA 0 mA = 0000 65535 (Hex FFFF) None 20 mA A196
14 OutFreq 4-20 4-20 mA 4 mA = 0 Hz [Maximum Freq] None 20 mA b001
15 OutCurr 4-20 4-20 mA 4 mA = 0 Amps 200% Drive Rated FLA Filter A 20 mA b003
16 OutTorq 4-20 4-20 mA 4 mA = 0 Amps 200% Drive Rated FLA Filter A 20 mA b013
17 OutVolt 4-20 4-20 mA 4 mA = 0 Volts 120% Drive Rated Output V None 20 mA b004
18 OutPowr 4-20 4-20 mA 4 mA = 0 kW 200% Drive Rated Power Filter A 20 mA b010
19 Setpnt 4-20 4-20 mA 4 mA = 0.0% 100.0% Setting None 20 mA T084
20 TstData 4-20 4-20 mA 4 mA = 0000 65535 (Hex FFFF) None 20 mA A196
21 MinFreq 0-10 0-10V 0V = Min. Freq [Maximum Freq] None 10V b001
22 MinFreq 0-20 0-20 mA 0 mA = Min. Freq [Maximum Freq] None 20 mA b001
23 MinFreq 4-20 4-20 mA 4 mA = Min. Freq [Maximum Freq] None 20 mA b001
24 AnlgIn1 0-10 0-10V 0V = 0.0% 100.0% Setting Filter A 10V d305
25 AnlgIn1 0-20 0-20 mA 0 mA = 0.0% 100.0% Setting Filter A 20 mA d305
26 AnlgIn1 4-20 4-20 mA 4 mA = 0.0% 100.0% Setting Filter A 20 mA d305
27 AnlgIn2 0-10 0-10V 0V = 0.0% 100.0% Setting Filter A 10V d306
28 AnlgIn2 0-20 0-20 mA 0 mA = 0.0% 100.0% Setting Filter A 20 mA d306
29 AnlgIn2 4-20 4-20 mA 4 mA = 0.0% 100.0% Setting Filter A 20 mA d306

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Allen-Bradley 22C-D038A103 and is the answer not in the manual?

Allen-Bradley 22C-D038A103 Specifications

General IconGeneral
BrandAllen-Bradley
Model22C-D038A103
CategoryController
LanguageEnglish

Related product manuals