14 Rockwell Automation Publication 2711P-UM006E-EN-P - January 2017
Chapter 1 Overview
400 and 600 Terminal
Features
Both the 400 and 600 terminals provide these communication options:
• RS-232 serial port only or
• Ethernet port and RS-232 serial port
Figure 1 - 400 Keypad or Keypad/Touch Terminals
Table 3 - PanelView Plus 6 - 400 Terminal Components
Item Component
1 3.5-in. grayscale or color display with one of these operator input options:
• Keypad
• Combination keypad and touch screen
2 Secure Digital (SD) card slot supporting cat. no. 1784-SDx cards
3a DC power input, nonisolated
(1)
24V DC nom (18…30V DC)
(1) Presence of a DC power input or AC power supply module is catalog number dependent. Removing the
AC power supply module voids the terminal warranty.
3b AC power supply module with AC power input
(1)
100…240V AC (50…60 Hz)
4 Mounting slots (four)
5 Ethernet port for controller communication, 10/100Base-T, Auto MDI/MDI-X
(2)
(2) Presence of Ethernet port is catalog number dependent.
6 RS-232 serial port for controller communication, printing, or file transfers
7 One USB 2.0 high-speed (type A) host port for attaching USB peripherals including
mouse, keyboard, printer, and USB drives that are hot-swappable in nonhazardous
locations
8 One USB 2.0 high-speed (type B) device port for connecting a host computer
9 Reset switch to reset the terminal without having to power off and on
10 Default switch to access maintenance operations such as restoring factory defaults
11 Battery compartment
12 Indicators provide communication and fault status