144 Rockwell Automation Publication 2711P-UM006E-EN-P - January 2017
Chapter 6 Terminal Connections
Serial Connections
The RS-232 serial port is multi-purpose and supports these connections:
DH-485 communication through a serial connection
DF1 full-duplex communication with controllers by using direct
connections or modem connections
Third-party point-to-point communication
Application transfers and printing
The serial port is a 9-pin, male, RS-232 connector. Ta ble 6 6
shows the pinout
descriptions and how these pins map to the serial ports on the controllers.
The maximum cable length for serial communication is 15.24 m (50 ft).
Figure 16 - RS-232 Serial Port
1
5
6
9
Insert plastic tie wrap in
the hole and use as strain
relief for all attached cables.
Table 66 - RS-232 Serial Port Connector Pinout
PanelView Plus 6 RS-232 Port
9-pin DCE
SLC or Logix
9-pin
PLC
25-pin
MicroLogix/
ENI 8-pin DIN
1
2
234
3
327
4
420
5
572
6
66
7
74
8
85
9
Connector Shell Chassis Gnd
WARNING: Do not connect or disconnect the communication cable with power
applied to the terminal, or the serial device on the other end of the cable. An
electrical arc could cause an explosion in hazardous location installations. Be
sure that power is removed or the area is nonhazardous before proceeding.
RXD
TXD
DTR
COM
DSR
RTS
CTS

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Allen-Bradley PanelView Plus 6 and is the answer not in the manual?

Allen-Bradley PanelView Plus 6 Specifications

General IconGeneral
BrandAllen-Bradley
ModelPanelView Plus 6
CategoryTouch terminals
LanguageEnglish

Related product manuals