When a reciprocating compressor is replaced:
Completely remove the oil from the system. The new
oil is not only more viscous. It is an ester oil with dif-
ferent chemical and physical properties.
!
!
NOTICE
Risk of damage to the compressor!
The new oil has a great cleaning effect in the re-
frigerant circuit.
On the suction side, mount a cleaning filter suit-
able for bidirectional operation!
Mesh size: 25µm
Mount a filter for bidirectional operation with perfor-
ated metal tubes around the inside and outside dia-
meter of the filter element.
After several operating hours: Change the oil filters
and cleaning filters.
If needed, repeat the operation, see chapter Oil
change, page 75.
4.6 Compressor start
4.6.1 Checking the rotation direction
!
!
NOTICE
Risk of compressor failure!
Operate the compressor only in the intended ro-
tation direction!
Even if the protection device SE-E1 or the optional pro-
tection device SE-i1 monitors the rotating field, a test is
recommended:
Rotation direction test with integrated suction shut-off
valve:
Connect the pressure gauge to the suction shut-off
valve. Close the valve spindle and open again by
one turn.
Let the compressor start shortly (approximately 0.5 ..
1s).
Correct rotation direction: Suction pressure drops im-
mediately.
Incorrect rotation direction: Suction pressure in-
creases or protection device shuts off.
Incorrect rotation direction: Change the poles of the
terminals on the common power supply line.
Direction rotation test without suction shut-off valve:
Close the solenoid valves on the evaporator and the
economiser. The pressure changes measured in
such a case are much lower than with throttled suc-
tion shut-off valve!
Let the compressor start shortly (approximately 0.5 ..
1s).
Correct rotation direction: Suction pressure drops a
bit.
Incorrect rotation direction: Suction pressure stays
the same or increases a bit, or protection device
shuts off.
Incorrect rotation direction: Change the poles of the
terminals on the common power supply line.
After the rotation direction test:
Let the compressor start while opening slowly the
suction shut-off valve.
4.6.2 Lubrication/oil level monitoring
Check the lubrication of the compressor directly after
the compressor start.
The oil level must be visible in the zone of both sight
glasses.
Check the oil level repeatedly within the first hours of
operation!
During the start phase, oil foam may arise but its
level should decrease at stable operating conditions.
Otherwise high proportions of liquid in the suction
gas are suspected.
!
!
NOTICE
Risk of wet operation!
Maintain the discharge gas temperature well
above the condensing temperature: at least
20K.
At least 30K for R407A, R407F and R22.
!
!
NOTICE
Risk of compressor failure due to liquid slug-
ging!
Before adding larger quantities of oil: check the
oil return!
4.6.3 Set high pressure and low pressure
switches (HP + LP)
Check exactly the cut-in and cut-out pressure values
according to the operating limits by testing them.
4.6.4 Set the condenser pressure
Set the condenser pressure so that the minimum
pressure difference is reached within 20s after the
compressor start.