No. Description
Setting
Unit Display conditions
Access
level
Enumeration
441 Direct expansion coil hour meter h
P28 Coil = Cooling direct expansion or heating direct
expansion or reversible direct expansion
1
446 DX unit defrosting status
0 : inactive
1 : active
P28 Coil = Cooling direct expansion or heating direct
expansion or reversible direct expansion
1
447 DX unit heating/cooling
0 : heating
1 : cooling
P28 Coil = reversible direct expansion 1
450 Recovery unit
0 : off
1 : on
1
451 Heat recovery unit operating-hour meter h 1
453 Recovery unit efciency %
472 Fault summary
0 : off
1 : on
1
490 Weekly programming request
0 : inactive
1 : active
1
491 State requested by the weekly programming
0 : off
1 : Frost protection
2 : Night cooling
3 : Setpoint 2 on
4: Setpoint 1 run
5: On
1
492 Annual programming request
0 : inactive
1 : active
1
493 State requested by the annual programming
0: off
1: Frost protection
2 : Night cooling
3 : Setpoint 2 on
4: Setpoint 1 run
5: On
11: Weekly prog. 1
12: Weekly prog. 2
13: Weekly prog. 3
14: Weekly prog. 4
15: Weekly prog. 5
16: Weekly prog. 6
1
9.4 - Faults level
No. Description
Setting
Display conditions
Access
level
Enumeration By default
602 intake lter 1 clogged
0 : Maintenance
1 : Danger
0 2
606 Exhaust lter 1 clogged
0 : Maintenance
1 : Danger
0 2
609 Manual electrical heater safety thermostat
0 : Maintenance
1 : Danger
1 P32 Electric heater = 2 On/Off stages 3
620 Supply air temperature too low
0 : Maintenance
1 : Danger
0 2
621 Supply air temperature too high
0 : Maintenance
1 : Danger
0 2
622 Return temperature too low
0 : Maintenance
1 : Danger
0 P146 Target temperature selection = return air 2
623 Return temperature too high
0 : Maintenance
1 : Danger
0 P146 Target temperature selection = return air 2
624 Room temperature too low
0 : Maintenance
1 : Danger
0 P146 Target temperature selection = room 2
625 Room temperature too high
0 : Maintenance
1 : Danger
0 P146 Target temperature selection = room 2
628 Duct pressure too low
0 : Maintenance
1 : Danger
0
P104 Air intake ventilation control = Duct
pressure
2
629 Duct pressure too high
0 : Maintenance
1 : Danger
0
P104 Air intake ventilation control = Duct
pressure
2
632 Loss of communication with energy meter
0 : Maintenance
1 : Danger
0 P40 Main box energy meter = With 2
635 Loss of communication with Th Tune
0 : Maintenance
1 : Danger
0 P149 = with 2
640 room temperature sensor
0 : Maintenance
1 : Danger
0 P149 = with 2
650 Intake FMA EC motor warning
0 : Maintenance
1 : Danger
0 2
651 Exhaust FMA EC motor warning
0 : Maintenance
1 : Danger
0 2
9 - PARAMETERS
FLOWAY ACCESS EN-56