9.5 - Communication parameters
No. Description
Setting
Unit Display conditions
Access
level
Enumeration By default
Communication parameters
BMS1
700
Selection of the type of communication protocol used on the
BMS1 port
0 : None
1 : ModBus RTU
2 : LON
3 : KNX
4 : ModBus TCP
5 : BACNET IP
6 : WEB
0 2
701 Selection of the transmission speed on the BMS1 port
0 : 1200
1 : 2400
2 : 4800
3 : 9600
4 : 19200
3 if P700=1 or 3
2 if P700=2
4 if P700=4, 5 or 6
P700 = 1 2
702 Parity on the BMS1 port
0: None
1 : odd
2 : even
0 P700 = 1 2
703 Number of stop bits on the BMS1 port 1 P700 = 1 2
704
705 Selection of the controller address on the BMS1 bus 1 P700 = 1 2
716 Control type
0: Local
1: Remote
1 2
BMS2
710
Selection of the type of communication protocol used on the
BMS2 port
1 : ModBus RTU 0 2
711 Selection of the transmission speed on the BMS2 port
0 : 1200
1 : 2400
2 : 4800
3 : 9600
4 : 19200
3 2
712 Parity on the BMS2 port
0: None
1 : odd
2 : even
0 2
713 Number of stop bits on the BMS2 port 1 2
714
715 Selection of the controller address on the BMS2 bus 1 P710 = 3 2
716 Control type
0: Local
1: Remote
0 2
pLAN
720 pCO address on the pLAN network 1 2
9.6 - Calibration
No. Description
Setting
Unit Display conditions
Access
level
Min. Max. Increment By default
Adjust. params
800 Calibration of the air intake fan ow rate sensor 2
801 Calibration of the air extraction fan ow rate sensor 2
802 Calibration of the supply air duct pressure sensor
P104 Air intake ventilation control = Duct
pressure
2
809 Calibration of supply air temperature sensor -5.0 5,0 0,1 0,0 °C 2
810 Calibration of fresh air temperature sensor -5.0 5,0 0,1 0,0 °C 2
811 Return air temperature sensor calibration -5.0 5,0 0,1 0,0 °C 2
813 Calibration of the room air temperature sensor -3.0 3,0 0,1 0,0 °C
P149 = with in read-only, modiable from
Th-Tune
2
816 Calibration of CO
2
Air Quality sensor -200 200 1 0 ppm P149 Air quality control = With 2
9 - PARAMETERS
EN-57 FLOWAY ACCESS

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the CIAT FLOWAY ACCESS and is the answer not in the manual?

CIAT FLOWAY ACCESS Specifications

General IconGeneral
BrandCIAT
ModelFLOWAY ACCESS
CategoryAir Handlers
LanguageEnglish

Related product manuals