No. Description
Setting
Unit
Access
level
Enumeration By default
Extraction FMA 1 information
2220 Calculated min. speed rpm 1
2221 Calculated max. speed rpm 1
2222 Speed requested rpm 1
2223 Current speed rpm 1
2224 Current consumed A 1
2225 Power input W 1
2226 Motor temperature °C 1
2227 Operating counter h 1
2230 Fault summary
0 : inactive
1 : active
1
2231 Communication state
0 : inactive
1 : active
1
2234 Warning summary
0 : inactive
1 : active
1
2235 Warning status 1
2238 Motor type 1
2239 Version number 1
9.9 - Energy meter
No. Description
Setting
Unit
Access
level
Enumeration By default
3000 Energy consumed 0 kWh 1
3001 Instantaneous power 0 W 1
3002 Voltage 0 V 1
3004 Voltage L1 - L2 0 V 1
3005 Voltage L3 - L2 0 V 1
3006 Voltage L1 - L3 0 V 1
3008 Current L1 0 A 1
3009 Current L2 0 A 1
3010 Current L3 0 A 1
3012 Fault summary
0 : Fault not present
1 : Fault present
1
3013 Communication state
0 : ofine
1 : online
1
3014 Serial number 1
3015 Version number 1
9 - PARAMETERS
EN-59 FLOWAY ACCESS

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the CIAT FLOWAY ACCESS and is the answer not in the manual?

CIAT FLOWAY ACCESS Specifications

General IconGeneral
BrandCIAT
ModelFLOWAY ACCESS
CategoryAir Handlers
LanguageEnglish

Related product manuals