- To download data from the LCP to the control card, select [2] All from LCP.
Press [OK].
A progress bar shows the uploading or downloading process.
Press [Hand On] or [Auto On].
7.5.3 Restoring Factory Default Settings Using the Recommended Initialization
N O T I C E
LOSS OF DATA
Restoring default settings results in a loss of programming, motor data, localization, and monitoring records.
To create a back-up, upload data to the LCP before initialization. See 7.5.2 Uploading and Downloading Parameter Settings.
Press [Main Menu] twice to access parameters.
Go to parameter 14-22 Operation Mode and press [OK].
Parameter 14-22 Operation Mode does not reset the following settings:
Running hours.
Serial communication options.
Personal menu settings.
Fault log, alarm log, and other monitoring functions.
Scroll to Initialization and press [OK].
Remove power to the unit and wait for the display to turn o.
Apply power to the unit. Default parameter settings are restored during start-up. Start-up takes slightly longer than normal.
After alarm 80, Drive initialized appears, press [Reset].
7.5.4 Restoring Factory Default Settings Using Manual Initialization
N O T I C E
LOSS OF DATA
Restoring default settings results in a loss of programming, motor data, localization, and monitoring records.
To create a back-up, upload data to the LCP before initialization. See 7.5.2 Uploading and Downloading Parameter Settings.
Procedure
Remove power to the unit and wait for the display to turn o.
Press and hold [Status], [Main Menu], and [OK] simultaneously while applying power to the unit (approximately 5 s or until
an audible click sounds and the fan starts).
Manually initializing does not reset the following parameter settings:
Parameter 15-00 Operating Hours
Parameter 15-03 Power Up's
Parameter 15-04 Over Temp's
Parameter 15-05 Over Volt's
Start-up takes slightly longer than normal.
AQ357954340588en-000201 / 130R0881 | 103Danfoss A/S © 2020.09
Commissioning
VLT® Refrigeration Drive FC 103
Operating Guide

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT FC 102 N250 and is the answer not in the manual?

Danfoss VLT FC 102 N250 Specifications

General IconGeneral
BrandDanfoss
ModelVLT FC 102 N250
CategoryDC Drives
LanguageEnglish

Related product manuals