10.6.6 Digital Inputs
Programmable digital inputs
4 (6)
Terminal number
(1)
XD2.12, XD2.13, XD2.14, XD2.15, XD2.16, XD2.17
Logic
PNP or NPN
Voltage level
0–24 V DC
Voltage level, logic 0 PNP
<5 V DC
Voltage level, logic 1 PNP
>10 V DC
Voltage level, logic 0 NPN
(2)
>19 V DC
Voltage level, logic 1 NPN
(2)
<14 V DC
Maximum voltage on input
28 V DC
Pulse frequency range
0–110 kHz
(Duty cycle) minimum pulse width
4.5 ms
Input resistance, R
i
Approximately 4 kΩ
1
Terminals XD2.14 and XD2.15 can also be programmed as output.
2
Except STO input terminal XD2.19.
All digital inputs are galvanically isolated from the supply voltage (PELV) and other high-voltage terminals.
10.6.7 Pulse/Encoder Inputs
Programmable pulse/encoder inputs
2/1
Terminal number (pulse inputs)
XD2.17
Terminal number (encoder inputs)
(2)
XD2.16, XD2.17
Maximum frequency at terminals XD2.15, XD2.16, XD2.17 (push-
pull driven)
110 kHz
Maximum frequency at terminals XD2.15, XD2.16, XD2.17 (open
collector)
5 kHz
Maximum frequency at terminals XD2.15, XD2.16, XD2.17
4 kHz
Voltage level
See Control Input/Output and Control Data.
Maximum voltage on input
28 V DC
Input resistance, R
i
Approximately 4 kΩ
Pulse input accuracy (0.1–1 kHz)
Maximum error: 0.1% of full scale
Encoder input accuracy (1–11 kHz)
Maximum error: 0.05% of full scale
2
Encoder inputs: XD2.16=A, XD2.17=B.
The pulse and encoder inputs (terminals XD2.15, XD2.16, XD2.17) are galvanically isolated from the supply voltage (PELV) and other
high-voltage terminals.
10.6.8 Control Characteristics
Resolution of output frequency at 0–590 Hz
±0.003 Hz
Repeat accuracy of precise start/stop (terminals XD2.12, XD2.13)
≤±0.1 ms
System response time (terminals XD2.12, XD2.13, XD2.14, XD2.15,
XD2.16, XD2.17)
≤2 ms
Speed control range (open loop)
1:100 of synchronous speed
Speed control range (closed loop)
1:1000 of synchronous speed
Speed accuracy (open loop)
30–4000 RPM: Error ±8 RPM
Speed accuracy (closed loop), depending on resolution of feed-
back device
0–6000 RPM: Error ±0.15 RPM
Torque control accuracy (speed feedback)
Maximum error ±5% of rated torque
AQ357954340588en-000201 / 130R0881150 | Danfoss A/S © 2020.09
Specications
VLT® Refrigeration Drive FC 103
Operating Guide

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT FC 102 N250 and is the answer not in the manual?

Danfoss VLT FC 102 N250 Specifications

General IconGeneral
BrandDanfoss
ModelVLT FC 102 N250
CategoryDC Drives
LanguageEnglish

Related product manuals