7.2.2 Parameter Navigation
Use the following LCP keys to navigate through the parameters.
Press [] [] to scroll up or down.
Press [] [] to shift a space to the left or right of a decimal point while editing a decimal parameter value.
Press [OK] to accept the change.
Press [Cancel] to disregard the change and exit edit mode.
Press [Back] twice to show the status view.
Press [Main Menu] once to go back to the main menu.
7.2.3 Programming Example for an Open-loop Application
This procedure, which is used to congure a typical open-loop application, programs the drive to receive a 0–10 V DC analog control
signal on input terminal 53. The drive responds by providing 20–50 Hz output to the motor proportional to the input signal (0–10 V
DC=20–50 Hz). The wiring connections used to enable the external device set-up are shown in Illustration 57.
Procedure
Press [Quick Menu].
Select Q3 Function Setups and press [OK].
Select Parameter Data Set and press [OK].
Select Q3-2 Open Loop Settings and press [OK].
Select Q3-21 Analog Reference and press [OK].
Select parameter 3-02 Minimum Reference. Set the minimum internal drive reference to 0 Hz and press [OK].
Select parameter 3-03 Maximum Reference. Set the maximum internal drive reference to 60 Hz and press [OK].
Select parameter 6-10 Terminal 53 Low Voltage. Set the minimum external voltage reference on terminal 53 at 0 V and press
[OK].
Select parameter 6-11 Terminal 53 High Voltage. Set maximum external voltage reference on terminal 53 at 10 V and press
[OK].
Select parameter 6-14 Terminal 53 Low Ref./Feedb. Value. Set minimum speed reference on terminal 53 at 20 Hz and press
[OK].
Select parameter 6-15 Terminal 53 High Ref./Feedb. Value. Set maximum speed reference on terminal 53 at 50 Hz and press
[OK].
With an external device providing a 0–10 V control signal connected to drive terminal 53, the system is now ready
for operation.
N O T I C E
SET-UP STATUS
When the scroll bar on the right of the display is at the bottom, the procedure is complete.
AQ357954340588en-000201 / 130R0881 | 99Danfoss A/S © 2020.09
Commissioning
VLT® Refrigeration Drive FC 103
Operating Guide

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT FC 102 N250 and is the answer not in the manual?

Danfoss VLT FC 102 N250 Specifications

General IconGeneral
BrandDanfoss
ModelVLT FC 102 N250
CategoryDC Drives
LanguageEnglish

Related product manuals