10 Specications
10.1 Electrical Data
10.1.1 Electrical Data, 380–480 V AC
Table 96: Electrical Data, Mains Supply 3x380–480 V AC
FC 102
N110
N132
N160
N200
N250
N315
Normal overload
110% torque for a duration of
60 s.
NO
NO
NO
NO
NO
NO
Typical shaft output at 400 V [kW]
110
132
160
200
250
315
Typical shaft output at 460 V [hp]
150
200
250
300
350
450
Typical shaft output at 480 V [kW]
132
160
200
250
315
355
Enclosure size
D9h
D9h
D9h
D10h
D10h
D10h
Output current (3-phase)
Continuous (at 400 V) [A]
212
260
315
395
480
588
Intermittent (60 s overload) (at
400 V) [A]
233
286
347
435
528
647
Continuous (at 460/480 V) [A]
190
240
302
361
443
535
Intermittent (60 s overload) (at
460/480 V) [A]
209
264
332
397
487
589
Continuous kVA (at 400 V) [kVA]
147
180
218
274
333
407
Continuous kVA (at 460 V) [kVA]
151
191
241
288
353
426
Continuous kVA (at 480 V) [kVA]
165
208
262
313
384
463
Maximum input current
Continuous (at 400 V) [A]
204
251
304
381
463
567
Continuous (at 460/480 V) [A]
183
231
291
348
427
516
Maximum number and size of cables per phase
- Mains [mm
2
(AWG)]
2x95 (2x3/0
mcm)
2x95 (2x3/0
mcm)
2x95 (2x3/0
mcm)
2x185 (2x350
mcm)
2x185 (2x350
mcm)
2x185 (2x350
mcm)
- Mains with disconnect [mm
2
(AWG)]
2x95 (2x3/0
mcm)
2x95 (2x3/0
mcm)
2x95 (2x3/0
mcm)
2x185 (2x350
mcm)
2x185 (2x350
mcm)
2x185 (2x350
mcm)
- Mains with fusible disconnect
[mm
2
(AWG)]
2x95 (2x3/0
mcm)
2x95 (2x3/0
mcm)
2x95 (2x3/0
mcm)
2x185 (2x350
mcm)
2x185 (2x350
mcm)
2x185 (2x350
mcm)
- Mains with contactor [mm
2
(AWG)]
2x95 (2x3/0
mcm)
2x95 (2x3/0
mcm)
2x95 (2x3/0
mcm)
2x185 (2x350
mcm)
2x185 (2x350
mcm)
2x185 (2x350
mcm)
- Motor [mm
2
(AWG)]
2x95 (2x3/0
mcm)
2x95 (2x3/0
mcm)
2x95 (2x3/0
mcm)
2x185 (2x350
mcm)
2x185 (2x350
mcm)
2x185 (2x350
mcm)
Drive module power loss at 400 V
[W]
(1)(2)(3)
2559
2954
3770
4116
5137
6674
AQ357954340588en-000201 / 130R0881 | 141Danfoss A/S © 2020.09
Specications
VLT® Refrigeration Drive FC 103
Operating Guide

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT FC 102 N250 and is the answer not in the manual?

Danfoss VLT FC 102 N250 Specifications

General IconGeneral
BrandDanfoss
ModelVLT FC 102 N250
CategoryDC Drives
LanguageEnglish

Related product manuals